Argo ULISSE ECO Manual de instalação - Página 11
Procurar online ou descarregar pdf Manual de instalação para Ar condicionado Argo ULISSE ECO. Argo ULISSE ECO 14 páginas. Room air conditioner with remote condenser
Também para Argo ULISSE ECO: Manual de Instruções (16 páginas)
12 - MATCH BETWEEN REMOTE CONTROLLER AND THE UNIT
The remote control can be addressed to use up to 4 different units installed in the same room.
You can get unified control by using a single remote control for all units or each remote control can be addressed to
its own unit, in order to control separately temperature, timer and all other functions.
UNIT
0
FACTORY STATE
1
2
3
PCB SETTING
• Disconnect the unit power supply and wait at least 60 seconds, mak-
ing sure that all the lamps go off.
• Remove the rear panel and the cover of the electrical box to access
the pcb.
• Set JP2 and JP3 as shown in the table.
• Close the cover of the electrical box and the rear panel.
• Reconnect the unit power supply.
REMOTE CONTROLLER SETTING
• Press the button
• Press the arrow
• Press the button
setting) at the bottom starts flashing.
• Press the arrow
• Confirm with the button
• Press
to exit the menu.
REMOTE CONTROL UNIT
11
for a few seconds.
until you visualize 06.
again for a few seconds: the number 0 (factory
to set 1, 2 or 3.
.
PCB
JP2=CLOSE JP3=CLOSE
JP2=OPEN JP3=CLOSE
JP2=CLOSE JP3=OPEN
JP2=OPEN JP3=APERTO
EN