113 (0x71)
The interval time of sending reports in Report group 3 (Valid values 0x05-
0x28DE80).
1. The unit of interval time is second if USB power.
2. If battery power, the minimum interval time is 60 minutes by default, for
example, if the value is set to be more than 5 and less than 3600, the interval
time is 60 minutes, if the value is set to be more than 3600 and less than 7200,
the interval time is 120 minutes. You can also change the minimum interval time
to 4 minutes via setting the interval value(3 bytes) to 240 in Wake Up Interval Set
CC.
201 (0xC9)
Temperature calibration (the available value range is [-100,100] or [-
10.0
℃
, 10
Note:
1. The value contains one decimal point. E.g. if the value is set to 20, the
calibration value is 2.0
2. The calibration value = standard value - measure value.
E.g. If measure value =25.3
calibration value= 23.2
If the measure value =30.1
value= 33.2
202 (0xCA)
Humidity sensor calibration (the available value range is [-50, 50]).
The calibration value = standard value - measure value.
E.g. If measure value =80RH and the standard value = 75RH, so the calibration
value= 75RH – 80RH= -5RH (0xFB).
If the measure value =85RH and the standard value = 90RH, so the calibration
value= 90RH – 85RH=5RH (0x05).
203 (0xCB)
Luminance sensor calibration (the available value range is [-1000, 1000]).
The calibration value = standard value - measure value.
E.g. If measure value =800Lux and the standard value = 750Lux, so the
calibration value= 750 – 800= -50 (0xFFCE).
If the measure value =850Lux and the standard value = 900Lux, so the calibration
value= 900 – 850=50 (0x0032).
204 (0xCC)
Ultraviolet sensor calibration (the available value range is [-10, 10]).
The calibration value = standard value - measure value.
E.g. If measure value =9 and the standard value = 8, so the calibration value= 8 –
9= -1 (0xFE).
If the measure value =7 and the standard value = 9, so the calibration value= 9 –
7=2 (0x02).
252 (0xFC)
Enable/disable Configuration Locked (0 =disable, 1 = enable).
Value=0x55555555
255 (0xFF)
Reset to factory default setting and removed from the z-wave network
2.Reset to factory default setting
Configuration Values for Parameter 101-103
7
℃
] ).
℃
(EU/AU version) or 2.0
℃
and the standard value = 23.2
℃
- 25.3
℃
= -2.1
℃
℃
and the standard value = 33.2
℃
- 30.1
℃
= 3.1
℃
(0x1F).
D efault=1
S ize=4
、
、
:
6
5
℉
( US version)
℃
, so the
(0xEB).
℃
, so the calibration
4
3
3600 (seconds)
4
0
1
0
1
0
2
0
1
0
1
N/A
4
N/A
1
2
1
0