Dinel CLS-23 Manual - Página 11

Procurar online ou descarregar pdf Manual para Acessórios Dinel CLS-23. Dinel CLS-23 20 páginas. Capacitive level sesors
Também para Dinel CLS-23: Manual de instruções (18 páginas)

Dinel CLS-23 Manual
8 .  s
ensor
settings
The setting is done by placing magnetic pen MP–8 to sensitive 
spot M located on the front of the sensor. Short time attaching 
(up  to  2  sec.)  of  the  magnetic  pen  to  the  sensitive  spot M
makes the sensor open. Long time attaching (at least 4 sec.) of 
the pen when the level is changed, defines closed state of the 
sensor. In this way is set the sensitivity for the measured medi-
um  and  switching  modes  SO  (normally  open)  or  SC  (normally 
closed).
Sensors of type CLS–23E are produced without signaling indicator LED. For control of correct 
settings it is necessary to interconnect the sensor to related evaluation unit or load.
In the case of the vertical mounting for detection of non-conductive liquids by sensors CLS–23_–20;
–30 and for detection of conductive and non-conductive liquids by sensors CLS–23_–21 it neces-
sary to set limits ON and OFF when electrode of the sensor is immersed to medium.
mode O 
(normally open)
mode C
(normally close)
FACTORY DEFAULT SETTINGS:
Types CLS–23_–10; –20; –30 are set to detect mineral oil, CLS–23_–11; –12; –21 to detect water. 
The mode O is set (sensor closes when immersed). 
9 .  s
tatUs
signalization
Indicator
Orange LED
© Dinel, s.r.o.
CLS–23
When the level is low (the container is empty), attach the magnetic pen 
MP–8 to the sensitive spot  M  for short time (max. 2 sec.). When the 
level is high (the container is full), attach the magnetic pen MP–8 to the 
sensitive spot  M  for long time (min. 4 sec.).
When the level is low (the container is empty), attach the magnetic pen 
MP–8 to the sensitive spot  M  for long time (min. 4 sec.). When the level 
is high (the container is full), attach the magnetic pen MP–8 to the sensitive 
spot  M  for short time (max. 2 sec.)..
(only with LED state indicator variant)
Function
Continuous light – Sensor is closed (switched ON)
Dark – Sensor is open (switched OFF)
Rapid flashing (period 0.2 s) – Unrecognized upper and lower limits or setting mistake
Slow flashing (period 0.8 s) – Short circuit at sensor output
Sensitive spot
11