The setting is done by placing magnetic pen MP–8 to sensitive
spot M located on the front of the sensor. Short time attaching
(up to 2 sec.) of the magnetic pen to the sensitive spot M
makes the sensor open. Long time attaching (at least 4 sec.) of
the pen when the level is changed, defines closed state of the
sensor. In this way is set the sensitivity for the measured medi-
um and switching modes SO (normally open) or SC (normally
closed).
Sensors of type CLS–23E are produced without signaling indicator LED. For control of correct
settings it is necessary to interconnect the sensor to related evaluation unit or load.
In the case of the vertical mounting for detection of non-conductive liquids by sensors CLS–23_–20;
–30 and for detection of conductive and non-conductive liquids by sensors CLS–23_–21 it neces-
sary to set limits ON and OFF when electrode of the sensor is immersed to medium.
mode O
(normally open)
mode C
(normally close)
FACTORY DEFAULT SETTINGS:
Types CLS–23_–10; –20; –30 are set to detect mineral oil, CLS–23_–11; –12; –21 to detect water.
The mode O is set (sensor closes when immersed).
9 . s
tatUs
signalization
Indicator
Orange LED
© Dinel, s.r.o.
CLS–23
When the level is low (the container is empty), attach the magnetic pen
MP–8 to the sensitive spot M for short time (max. 2 sec.). When the
level is high (the container is full), attach the magnetic pen MP–8 to the
sensitive spot M for long time (min. 4 sec.).
When the level is low (the container is empty), attach the magnetic pen
MP–8 to the sensitive spot M for long time (min. 4 sec.). When the level
is high (the container is full), attach the magnetic pen MP–8 to the sensitive
spot M for short time (max. 2 sec.)..
(only with LED state indicator variant)
Function
Continuous light – Sensor is closed (switched ON)
Dark – Sensor is open (switched OFF)
Rapid flashing (period 0.2 s) – Unrecognized upper and lower limits or setting mistake
Slow flashing (period 0.8 s) – Short circuit at sensor output