Whirlpool CGW9100VQ0 Manual de instalação - Página 11
Procurar online ou descarregar pdf Manual de instalação para Secador Whirlpool CGW9100VQ0. Whirlpool CGW9100VQ0 40 páginas. Commercial dryer- gas or electric
[]
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per
dryer. Large-capacity
lint screens of proper design may be
used in the main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than the CFM of all the dryers in the room.
[]
Back-draft Damper Kit, Whirlpool Part No. 3391910, is
available from your dealer and should be installed in the vent
of each dryer to prevent exhausted air from returning into the
dryers and to keep the exhaust in balance within the main
vent. Unobstructed
air openings are required.
Each vent should enter the main vent at an angle pointing in the
direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering
with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30 °.
A
air flow
_
B
_---
A. Individualdryervent
B. Mainvent
Keep air openings free of dry cleaning fluid fumes. Fumes create
acids which, when drawn through the dryer heating units, can
damage dryers and loads being dried.
A clean-out cover should be located on the main vent for periodic
cleaning of the vent system
If an exhaust hood cannot be used:
B
A
U
°
O_
_
................
E
G.Roof
2 ft. (61 cm) min.
above highest
point of building
The outside end of the main vent should have a sweep elbow
directed downward. If the main vent travels vertically through the
roof, rather than through the walt, install a 180° sweep elbow on
the end of the vent at least 2 ft. (61 cm) above the highest part of
the building. The opening in the wall or roof shall have a diameter
1Z2" ( 1.3 cm) larger than the vent diameter. The vent should be
centered in the opening.
Do not install screening or cap over the end of the vent.
INSTALLATION INSTRUCTIONS - COINSLIDEANDCOINBOX
The console houses the factory-installed
accumulator
timer with
actuating arm and button.
The factory-installed
timer is set to provide 45 minutes (4 pins)
of drying time when activated by the coin slide. Timer cams for
30-minute (6 pins) and 60-minute (3 pins) drying times are
included in the parts bag.
The coin slide mechanism, control panel lock and key, and coin
box lock and key are not included and are available from usual
industry sources.
Excessive Weight Hazard
Use two or more people to move and install dryer.
Failure to do so can result in back or other injury.
NOTE: Slide dryer onto cardboard or hardboard before moving to
avoid damaging floor covering.
1. Using two or more people, move dryer to desired installation
location.
2. Take tape off front corners of dryer. Open dryer and remove
the literature and parts packages. Wipe the interior of the
drum thoroughly with a damp cloth.
3=
4=
5=
6=
7=
8.
Take two of the cardboard corners from the carton and place
them on the floor in back of the dryer. Firmly grasp the body
of the dryer and gently lay it on its back on the cardboard
corners.
With one of the legs in hand, check the ridges for a diamond
marking. That's how far the leg is supposed to go into the
hole.
Start to screw the leveling legs into the holes by hand. (Use a
small amount of liquid detergent to lubricate the screw
threads so it is easier to turn the legs.) Use a 1" wrench or
socket wrench to finish turning the legs until you reach the
diamond mark.
Now stand the dryer up.
Remove the service
door of the meter case
by lifting it up at the
back. Install the money-
accepting device. (Refer
to manufacturer's
instructions for proper
installation.)
For dryers using coin
slides, use the adapter kit supplied with the dryer.
Replace the meter case service door. Put the coin vault with
lock and key in the meter case opening.
Remove cardboard or hardboard from under dryer.the legs of
the dryer up or down until the dryer is level.
11