17. Fire/Fault Delay

These settings are the delays that the System Controller uses before signalling a FIRE or
FAULT condition respectively to the Fire Control Panel. Default factory setting=10 seconds
(Set for each Detector)

18. Latching/Non-Latching Mode

In Latching Mode the system will stay in Fire condition after the fire clears. In Non-Latching
Mode the system will automatically return to normal condition after the fire clears
(Set for each Detector)
To clear a latched fire, apply 5-40V to the External Reset terminal, enter the passcode, or
power cycle for 20s
Delay 1 (Fire)
Non-Latching
Latching
Use
to move between icons in the
Detector Menu, until the graph and bell icons
are shown
13
Delay 2 (Fault)