Installation
1. Turn power OFF to disable the 0–10 V- electronic ballast(s)/driver(s) to be dimmed.
WARNING: Shock hazard. May result in serious injury or death. Turn o power at
circuit breaker before installing the control.
2. Remove wallplate, slider, and wallplate adapter (if using o set mounting holes) from
control to prevent surface damage and to access mounting holes.
3. Strip wallbox wires to the following lengths:
4. Wire controls according to the appropriate wiring diagram shown in the Wiring section
and on the ballast/driver.
Note: The total 0–10 V- control signal wiring for this control should not exceed 500 ft
(152.4 m). Do not use wire smaller than 20 AWG (0.75 mm
For Class 1 installations: 0–10 V- wires must be run in conduit or approved cable
per NEC or local jurisdiction.
For Class 2 installations: Conduit is typically not required (local codes may apply).
For applications with excessive electrical noise: 0–10 V- wires should be run in
conduit separate from the mains.
Wallbox Wiring
To Ballasts
Wallbox
Violet
Gray
Green
Green or Bare
Switching
Black
Wires
5. Carefully push wires into wallbox, allowing room for the control back cover.
6. Mount control into wallbox using screws provided. Controls must be mounted vertically.
7. Turn power ON. Pushing slider up should increase light intensity; pushing slider down
should decrease light intensity.
8. The maximum light level intensity may be adjusted as follows:
a. Push slider to the top-most position. If using with uorescent ballasts, run lamps for
15 minutes to warm lamps. Remove the plastic slider to expose the trim adjustment
screws.
b. Maximum light intensity is initially set at the factory to the maximum setting. Use a
small screwdriver to turn the high-end trimpot screw clockwise to decrease light level
and counterclockwise to increase light level.
9. The minimum light level intensity may be adjusted as follows:
a. Push slider to the bottom-most position. Remove the plastic slider to expose the trim
adjustment screws.
b. Use a small screwdriver to turn the low-end trimpot screw clockwise to increase light
level and counterclockwise to decrease light level.
10. Mount wallplate adapter plate with screws provided. Replace slider and snap on
wallplate.
Wiring
Manor-2101 Control Class 1 Installation
Neutral
2
) wire
2
) wire
120 – 277 V ~
).
2
Line
Black
Low-end
Manor-2101 Control Class 2 Installation
Trimpot Shaft
On/O Control using Power Pack (PP-120H, PP-277H, or PP-347H)
Neutral
High-end
Trimpot Shaft
120 – 277 V ~
Line
IEC PELV/NEC
Class 2 wiring:
(0.75 mm
2
)
Black
Black
Control
Green
Notice: Alcon Lighting is not liable for damage due to miswiring 0–10 V- control signal wires with line voltage.
Do not run Class 2 wires and line voltage conductors together in the same conduit.
Maximum Capacity
(Limited by whichever is achieved rst)
Load
8 A
White
Black
Violet (+)
Gray (–)
White
Black
Black
Violet (+)
Violet (+)
Gray (–)
Gray (–)
Control
Class 1
0 – 10 V -
To additional
control signal
Ballasts or
Green
wires *
Drivers
* Do NOT connect to line voltage.
Maximum Capacity for Class 2 Installations
Red
3
Load
5 A
1
Black
White
Red
3
Black
®
2
White
Power
Pack
Black
Violet (+)
Gray (–)
Red
Black
Blue
(capped-o )
White
Black
Violet (+)
Violet (+)
Gray (–)
Gray (–)
1
Multiple power packs can be used in parallel for
Class 2
higher loads.
0 – 10 V -
To additional
2
Do NOT connect to line voltage.
control
Ballasts or
3
18 AWG (1.0 mm
4
signal wires
2
Drivers
Connect either one to line/load side.
4
Green wire may be capped-o for Class 2
installations only.
Troubleshooting
Problem
Lights do not
0 – 10 V - Sink
operate at full
brightness
30 mA
0 – 10 V - Dimming Ballast
or LED Driver
Lights do not
dim low
enough
Ground
0 – 10 V - Dimming Ballast
or LED Driver
Ground
Lights do not
dim at all
0 – 10 V - Sink
30 mA
0 – 10 V - Dimming Ballast
or LED Driver
Ground
0 – 10 V - Dimming Ballast
or LED Driver
Ground
2
) red wires are interchangeable.
Possible Solution
Push slider up. Turn trimpot counterclockwise
with a small screwdriver to achieve maximum
light intensity.
Check to see that violet and gray wires are
not cross-connected in any xture, conduit, or
wallbox.
Push slider down. Turn trimpot
counterclockwise with a small screwdriver to
achieve minimum light intensity.
Check to see that violet and gray wires are not
cross-connected in any xtures.
Check the lamp or LED output with a light
meter in the absence of other sources of
illumination (or correct for other sources)
at both high- and low-light readings. The
low-end light output may be limited by the
ballast or LED driver. Check the manufacturer' s
speci cations.
Check to see that the violet and gray wires are
not disconnected in any xtures.