AM Series Thermal Insulation Replacement Instruction
5.
Referring to Figure 3, unscrew nut "H." Take note of the gasket between nut "H" and the
gas valve.
Figure 3: Removing the Nut & Spring from the Gas Valve
6.
Disconnect the electrical plug from the gas valve.
7.
Use a screwdriver to remove the spring labeled "A."
8.
Referring to Figure 4, remove the gas valve from its position. Note the O-ring, labeled "L."
07/28/2014
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Kit # 62632006
Removing the Burner – Continued
Figure 4: Removing the Gas Valve