Camille Bauer SIRAX B 811 Manual de início rápido - Página 3
Procurar online ou descarregar pdf Manual de início rápido para Unidade de controlo Camille Bauer SIRAX B 811. Camille Bauer SIRAX B 811 10 páginas. Plug-in module power pack with additional functions
Signalling modes
Output signals
A1 and A12:
Frontplate signals:
Output contact AF:
Table 2: Type of output contact
Symbol
Material
Gold flashed
silver alloy
Relay approved by UL, CSA, TÜV, SEV
Direction of action:
Adjustable by switch
– Relay "energized" or "de-energized"
in the case of a failure
Accuracy data (acc. to DIN/IEC 770)
Basic accuracy:
Reference conditions:
Ambient temperature
Power supply
Output burden
Influencing factors:
Temperature
Burden influence
Camille Bauer
Power Pack with Additional Functions
– Output signal linear response
For an open-circuit output
0 mA (with 4...20 mA)
– 5 mA (with 0...20 mA)
For a short-circuit
output approx. 26 mA
– Increasing output signal
Output approx. 115% of full-scale
value, e.g. 23 mA for output
0/4...20 mA
or
11.5 V for output 0/2...10 V
– Decreasing output signal
(only possible for live zero)
Output approx. 10% of full-scale
value, e.g.
output 4...20 mA
or 1 V for output 2...10 V
Failure signalled by red LED
1 relay, 1 potentially-free changeover
contact (see Table 2)
Contact rating
AC: ≤ 2 A / 250 V
(500 VA)
DC: ≤ 1 A / 0.1...250 V
(30 W)
Limit error ≤ ± 0.2%
Including linearity and reproducibility
errors
23 °C, ± 2 K
24 V DC ± 10% and
230 V AC ± 10%
Current: 0.5 · R
max.
ext
Voltage: 2 · R
min.
ext
< ± 0.1% per 10 K
< ± 0.1% with current output
< 0.2% with voltage output,
if R
> 2 · R
min.
ext
ext
Data sheet B811-6 Le – 09.07
Plug-in Module SIRAX B 811
Long-time drift
Switch-on drift
Common and transverse
mode influence
Output + or –
connected to ground:
Standards
Electromagnetic
compatibility:
Intrinsically safe:
Electrical standards:
Protection (acc. to IEC 529
resp. EN 60 529):
Operating voltage:
Rated insulation voltage:
Contamination level:
Overvoltage category
acc. to IEC 664:
Electrical insulation:
:
Test voltage:
Environmental conditions
Commissioning
temperature:
Operating temperature:
Storage temperature:
Annual mean
relative humidity:
Altitude:
Indoor use statement!
< ± 0.3% / 12 months
< ± 0.2%
< ± 0.2%
< ± 0.2%
The standards DIN EN 50 081-2 and
DIN EN 50 082-2 are observed
Acc. to DIN EN 50 020: 1996-04
Acc. to IEC 1010 resp. EN 61 010
Housing IP 40
Terminals IP 00
Measuring input < 30 V
Measuring outputs < 25 V
Output contact,
Power supply < 250 V
253 V AC for all circuits
2
III for power supply
II for measuring input, measuring
output and output contact
Power supply versus all other cir-
Power supply versus all other cir-
Power supply versus all other cir-
cuits,
measuring input versus measuring
output and output contact
Power supply versus measuring
input, measuring output and output
contact 3.7 kV, 50 Hz, 1 min.
Measuring input versus measuring
output 2.3 kV, 50 Hz, 1 min.
Measuring output versus output
contact 2.3 kV, 50 Hz, 1 min.
– 10 to + 40 °C
– 25 to + 40 °C,
Ex –20 to + 40 °C
– 40 to + 70 °C
≤ 75%
2000 m max.
3