Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output
Follower Mode
Temporal Code 3
Mode
Steady Mode
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
Function
Amseco

Sync Mode*

Faraday
Sync Mode*
Gentex
Sync Mode*
Gentex is a registered
trademark of Gentex Corporation.
System Sensor
Sync Mode*
System Sensor is a registered
trademark of Honeywell.
Wheelock
Sync Mode*
Note: The AL1042UL2ADA will only synchronize horns, horn strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs.
*It is required to control visual notification appliances (strobes) via input 1 [IN1] and audible notification
appliances (horns) via input 2 [IN2]. This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
- 4 -
Switch Positions
Descriptions
ON
OFF
1
2, 3
Output follows signal it receives from the corresponding input
(i.e. FACP Sync module - maintains synchronization of
notification appliance circuit.
3
1, 2
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
1, 2, 3
A steady output signal will be generated. This mode
will accept steady or pulsing input.
Switch Positions
Descriptions
ON
OFF
1, 3, 4
2
This mode is designed to work with the Amseco
series of horns, strobes, and horn/strobes to provide a means of syn-
chronizing the Temporal-coded horns, synchronizing the flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
2, 4
1, 3
This mode is designed to work with the Faraday
series of horns, strobes, and horn/strobes to provide a means of syn-
chronizing the Temporal-coded horns, synchronizing the flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
1, 2,
This mode is designed to work with the Gentex
3, 4
and ST/HS series of horns, strobes, and horn/strobes to provide a
means of synchronizing the Temporal-coded horns, synchronizing the
flash timing of the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving strobes active.
1, 2, 4
3
This mode is designed to work with the SpectrAlert
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
2, 3, 4
1
This mode is designed to work with the Wheelock series of
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
(AL842LGK Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
®
Commander GOS
TM
series of
AL1042UL2ADA