Altronix AL1042UL2ADA Manual de instalação - Página 5

Procurar online ou descarregar pdf Manual de instalação para Extensor Altronix AL1042UL2ADA. Altronix AL1042UL2ADA 12 páginas. Nac power extender

Terminal Identification Table:
AL842LGK Logic Board
Terminal
Function/Description
Legend
IN1+, IN1-
These terminals connect to the 12 or 24VDC FACP notification appliance circuit outputs. (Class A or
IN2+, IN2-
Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is shown in alarm condition.
During an alarm condition these inputs will cause the selected outputs chosen to drive notification
appliances. The designated outputs are set by output switches [OUT1 through OUT4] (Output
Programming Selection Table, pg. 4). A trouble condition on an output loop will cause the corresponding
input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble
to drive notification appliances.
RET1+, RET1- For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B hookups
RET2+, RET2- the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals.
Optionally, other notification appliances or additional signaling circuit power supplies may be connected
to these terminals. If this option is chosen the EOL resistor must be terminated at the last device.
C "DRY1" NC
An open across these inputs, will cause the selected outputs chosen to drive
C "DRY2" NC
notification appliances. The designated outputs are set by output switches [OUT1 through
(Dry input
OUT4] (Output Programming Selection Table, pg. 4). Note these inputs are
trigger)
unidirectional and will not report a trouble condition to the FACP.
+ OUT1 - -
Notification appliances are connected to these outputs (see Application Guide, pgs. 2-4).
+ OUT2 - -
Each power limited output will supply 2 amp. Two (2) outputs may be connected in parallel for a
+ OUT3 - -
maximum NAC output capability of 4 amp. Total supply current is 6.5 amp (see note below). Outputs
+ OUT4 - -
are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Prog. Selection Table, pg. 4).
+ Loop 1 - -
Used for class A hook-ups to terminate loops originating on [OUT1, OUT2, OUT3 and OUT4]
+ Loop 2 - -
respectively.
+ Loop 3 - -
+ Loop 4 - -
C "FAULT" NC An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously signal a trouble
(Common
condition back to the FACP (Typically used to report AC or BAT Fail).
trouble input)
(Fig. 2D, pg. 7).
NC, C, NO
These are dry contact trouble outputs that report any general loop/system trouble conditions.
(Common
(Typically used to trigger a digital communicator or other reporting device).
trouble output) (form "C" contact 1 amp / 28VDC) (Fig. 2D, pg. 7).
- - AUX1+
This separate auxiliary output supplies up to 1 amp continuous under normal AC powered conditions.
It will be disconnected from its load during AC power failure (Fig. 2D, pg. 7).
- AUX2+
This separate 1 amp max. Auxiliary output will provide up to 1 amp stand-by current for 24 hours and
up to 1 amp in alarm condition. It supplies up to 1 amp continuous under normal AC powered
conditions (Battery Calculation Worksheet, pg. 9).
Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: "AUX1" will automatically disconnect when
AC is lost. "AUX2" will remain battery backed up during power outage. For loads connected to "AUX2" please, refer
to battery "Stand-by Specifications" above for ratings. When loads are connected to the "AUX1" and or "AUX2" out-
puts during alarm condition, the remaining outputs may, not exceed 10 amp total alarm current.
(example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 8 amp).
AL1042UL2ADA
- 5 -