AERMEC PCO5 Manual do utilizador - Página 14
Procurar online ou descarregar pdf Manual do utilizador para Painel de controlo AERMEC PCO5. AERMEC PCO5 20 páginas.
7.10 SETTINGS FREE GLYCOL FREECOOLING
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the value in kW declared for freecooling (circuit 1)
— Indicates the value in kW declared for freecooling (circuit 2)
— Indicates the value in kW declared for freecooling (circuit 3)
— Indicates the value in kW declared for freecooling (circuit 4)
— Indicates the value of compressor 1 in kW
— Indicates the value of compressor 2 in kW
— Indicates the value of compressor 3 in kW
— Indicates the value of compressor 4 in kW
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 1 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 2 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 3 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 4 is declared
— Indicates the outlet temperature from the freecooling coil below which the fans
are inhibited
— Indicates the differential (applied to the freecooling coil output) beyond which
the fans are enabled at maximum speed
— Indicates the forcing time for the glycol pump at start-up
— Indicates the activation set of the anti-freeze resistance for the glycol side
7.11 CONFIGURING THE C-TOUCH CLOCK AND THE PCO5
CLOCK
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current day of the week on the C-Touch timer
— Indicates the current time on the C-Touch timer
— Indicates the current date on the C-Touch timer
— Indicates the current time on the pCO5 timer
— Indicates the current date on the pCO5 timer
— Indicates the time to set on the pCO5 timer
— Indicates the date to set on the pCO5 timer
— Allows setting the specified date and time on the pCO5 board
14
7.12 SOFTWARE VERSION
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current software version for the pCO5 card