1.5
Automatic humidity controlled boost activation/inactivation (for adjustment see 5.12)
From the home screen, press and hold "SET" and "COPY" simultaneously for 3 seconds
Press "COPY" as required to move to 'Menu 7' 'IhuN'
Use the "+" or "-" button to set to 'on' or 'off' (OF) as required
Press "SET" to record or "ESC" to discard the settings and return to the home screen
1.6
Filter reminder adjustment/inactivation
From the home screen, press and hold "SET" and "COPY" simultaneously for 3 seconds
Press "COPY" as required to move to 'Menu 1' 'Filter'
Use the "+" or "-" buttons to change the time delay in steps of 50 hours as required or 'off'.
Note: The filter check reminder is factory set at the maximum of 3000 hours (approx.
4months - recommended). During adjustment, when this maximum has been reached, the
'off' option can be accessed.
Press "SET" to record or "ESC" to discard the settings and return to the home screen
1.7
Frost protection trigger temperature adjustment
From the home screen, press and hold "SET" and "COPY" simultaneously for 3 seconds
Press "COPY" as required to move to 'Menu 4' 'T5'
Menu T5 sets the frost protection trigger temperature between -15°C and +5°C (Factory
default +1°C)
Use the "+" or "-" buttons to set the trigger temperature in steps of 1°C
LAB1306R, Issue 1, March 2018
V E N T I L A T I O N
Page 20
Page 7