HOLD OPEN TIME **
open and no other activation is received.
DOOR BRAKING **
location, the motor is decelerated to halt motion. This parameter
is a hard DECELERATION this is for HEAVY DOORS ONLY.
THIS IS NOT TO BE USED IN CONJUCTION WITH
DECELERATION leave this set to default unless your door is so
heavy that it will not slow for check speed and runs into the stop
or slams shut.
Handing **
When the door is 1 st activated and starts the learning cycle we
want the door to travel to the full open position first. If the door
tries to close first you must change the handing direction.
LOCK TYPE ** Sets controller to operate either FAIL SAFE or
FAIL SECURE lock
BREAKOUT POLARITY ** Depending on what type of
switches your door has, either Normally Open or Normally
Closed contacts. If the breakout panels are closed and the
orange LED marked B-Out
(located below connector J7) is illuminated the door cannot be
activated. CHANGE POLARITY.
LOCK DELAY **
Delay is for 1 second. When an activation signal is received the
door will be delayed from opening while the lock is being
disengaged.
LOAD FACTORY DEFAULTS **
Pressing the program key will reset a setting to factory
defaults
PLEASE NOTE: ABOVE ITEMS MARKED WITH ** CAN ONLY BE AJUSTED
IN PROGRAM MODE. To access program mode, Press and hold the
program button. While the programming button is pressed, press and
release the reset button then release the programming button.
After making changes, press RESET to exit program mode.
The control will perform a learn cycle on the first activation after reset.
Amount of time that the door remains
When the door reaches the check
Handing sets the direction polarity of the motor.
Set to ON if the door has an electric lock.