2.6 nrgCONTROL Connectivity

The nrgCONTROL panel utilizes the LAN port located on the front of the unit to connect the controller to the data storage
location.
The controller can be operated in the following modes simultaneously:
1. Local Only Mode
The controller will collect data from all panel sensors that are connected to it over nrgNET interface
No SNMP traps or data is sent for monitoring
The instantaneous sensor data can be viewed from the front of the controller's LCD screen for all attached
monitoring panels
2. SNMP Mode
The LAN port must be connected and configured to operate on the same subnet as the customer defined
SNMP/NMS server address
The nrgSMART MIB table is available for download at the following URL:
www.telect.com/NewProductDetail/nrgsmart-controller
SNMP traps can be set-up for current threshold crossings, breaker trips or blown fuses, voltage threshold
crossings and temperature threshold crossings
Sensor data and configuration data can be polled by issuing commands from the NMS
The NMS will have to manage and store all collected data
The nrgCONTROL-BT uses a static IP address of 192.168.1.1 with a subnet mask of 255.255.255.0. Set up your PC or
server to an address on the same subnet as the nrgCONTROL-BT. To do this, follow the steps below:
1. Connect a CAT5 cable to the front panel LAN connector of the nrgCONTROL-BT panel.
2. Go into Network Settings from either the Control Panel or the Network icon in the bottom right corner of the task bar
on your PC.
NOTE: There will be different paths to get to these settings based on your operating system.
3. Double-click Ethernet or LAN connection.
4. Select Internal Protocol Version 4 (TCP/IPv4).
5. Change your settings from Obtain an IP Address Automatically to Use the Following IP Address in the subnet range of
192.168.1.2 – 192.168.1.254 subnet mask of 255.255.255.0; no gateway or DNS needed.
6. Hit OK on the next two screens to complete the change.
7. Open the nrgCONTROL-BT via a browser by its IP address of 192.168.1.1.
NOTE: Chrome is recommended browser. Other supported browsers include Firefox.
8. The Configuration Wizard will be displayed.
For connecting and configuring your nrgSMART panels, please refer to nrgSMART Configuration Guide.
nrgCONTROL-BT
RJ-45 LAN port

Fig. 8: LAN port location

9
Amphenol Telect
All rights reserved. 07.20.2018 145122-4