Carlin 60200FR Руководство по установке и эксплуатации
Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Блок управления Carlin 60200FR. Carlin 60200FR 8 страниц. Gas burner primary control
Также для Carlin 60200FR: Руководство по установке и эксплуатации (9 страниц)

• On-Board LCD Screen
• Fully Programmable Settings
• 32 Cycle Fault History
• Alarm Contacts
• Serviceman Reset Protection
• Blocked Vent Protection
• Provides Flame Signal in Microamps
• Low Voltage Terminals
It is important that the installation of the oil burner,
piping and fittings, safety devices, controls, electrical
wiring and equipment be done in accordance with
national and/or local regulations of the authorities
having jurisdiction over such installation.
©
Copyright 2020 — Carlin Combustion Technology
Model 60200FR
Gas Burner
Primary Control
Installation and
Operating Instructions
For Use By Qualified Service Technicians Only
Power input
(red/white wire) ................................ 120 VAC, 60 HZ, 9 VA
Limit circuit input
(black wire) .............................................. 120 VAC, 60 HZ
Motor load
(orange wire) .........10 FLA / 60 LRA (reduce by valve load)
Ignitor load
(blue wire) .................................... 120 VAC, 60 HZ, 500 VA
Valve load
(violet wire) .......................................... 120 VAC, 60 HZ, 2A
Auxiliary ..................................................... 120 VAC, 1 amp
Operating voltage ................................120 VAC - 132 VAC
Alarm contacts (dry contacts)....................24V, AC/DC, 2A
Operating temperature limits ..................+32°F to +140°F
Thermostat ..................................................... 24 VAC, 0.1A
Blocked Vent ................................................. 12 VDC, 2mA
CO .................................................................. 12 VDC, 2mA
Agencies .............................. UL recognized (US & Canada)
FROZEN PIPES/WATER DAMAGE
This is not a freeze protection device. Suitable freeze protection
monitoring or other precautions are recommended to protect
against ruptured pipes/water damage caused by fuel outage,
safety related fault conditions or equipment failure.