Carlin 60200FR Руководство по установке и эксплуатации - Страница 6

Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Блок управления Carlin 60200FR. Carlin 60200FR 8 страниц. Gas burner primary control
Также для Carlin 60200FR: Руководство по установке и эксплуатации (9 страниц)

Carlin 60200FR Руководство по установке и эксплуатации
SETTING
MODE
OPTIONS
PRESS THE
BUTTONS
TO
CHANGE
SETTINGS
Shaded box = default setting.
** MA Code ("N" models) are non-recycling and will lock out on flame failure.
**Changing this setting to 'Yes', with limits powered will exit Settings mode and result in immediate 'Call For Heat'.
If flame is sensed during Pre-Purge, control will go to Lockout immediately – except when Pre-Purge is set to 0 Sec.
*
† †
If TFI fails after first recycle, control will lockout, regardless of "Allowed Recycles" setting.
• Pre-Purge: Time period motor and ignitor are on prior to Trial for
Ignition. Note: If flame is sensed during Pre-Purge, control will go
to Lockout immediately.
• Trial for Ignition: Flame-establishing period during ignition. If
flame is not established, the control will recycle. The next cycle
will be a set 60 second Pre-Purge. If TFI fails on the next cycle,
control will go to Lockout.
• Post-Purge: Time period the motor is on after the Call for Heat is
satisfied to allow for evacuation of combustion gases. A call for
heat during Post-Purge will result in a recycle.

Operating Sequence

With power to the control and the gas valve open, set
thermostat (and limit) to call for heat. NOTE: The thermostat
circuit must be closed and power must be coming to black
wire from limit circuit.
During Pre-Purge, the motor starts.
Pre-Purge
Following Pre-Purge, the control advances to a
3 second Pre-Ignition
Pre-Ignition
During Pre-Ignition, the ignitor turns on and enters Trial for
Ignition.
Trial for Ign
6
A V A I L A B L E
PRESS THE
BUTTON TO VIEW DIFFERENT SETTING MODES
Trial for
Pre-Purge
Post-Purge
Ignition
0 Sec
4 Sec
0 Sec
10 Sec
6 Sec
10 Sec
30 Sec
15 Sec
90 Sec
30 Sec
60 Sec
2 min
Setup Menu Definitions
X X Sec
X X Sec
X X Sec
SEE STATUS ICONS – PAGE 8
S E T T I N G S
TT
Allowed
Clear Fault
Jumpered
Recycles
History
††
Internal**
None*
Yes
Yes
1
No
No
3
• Allowed Recycles: Number of Recycles allowed during a single
Call for Heat prior to Lockout.
• TT Jumpered Internal: Allows TT to be "jumpered" by software
program.
• Clear Fault History: Allows all prior burner fault conditions stored
in control to be cleared.
• Restore Factory Defaults: Allows all factory defaults to be
restored in control (refer to settings shaded in gray in the table
above). Will reset and reboot control .
During Trial for Ignition, the gas valve opens. When flame is
detected, the screen will briefly display "Flame Detected" and
then procedes to Burner Running
Burner Running
When the Call for Heat ends (or a limit control interrupts the
burner circuit), the gas valve will turn off. The motor remains
on for the Post-Purge period. When the Post-Purge timer
expires, the control returns to Standby mode awaiting the
next call for heat.
Post-Purge
Standby
No Call for Heat
Restore
Factory
Defaults
Yes
No
5 9 Sec
X X Sec
5 9 Sec
Carlin Combustion Technology