NOTE: Depending upon module configuration, some parameters in the Main
and Running Editors may not be available. For more information refer to DSE
publication 057-239 DSE8610 MKII Configuraiton Suite PC Software Manual
available from www.deepseaplc.com

MAIN CONFIGURATION EDITOR PARAMETERS

Section
Parameter As Shown On Display
Values
Display
Contrast
0%
Language
English, Other.
Current Date and Time
DD:MM:YY, hh:mm:ss
Alt Config
Default Config
Default Config / Alternative Config
Engine
Oil Pressure Low Shutdown
0.00 bar
Oil Pressure Low Pre Alarm
0.00 bar
Coolant Temperature Low Warning
0 ºC
Coolant Temp High Pre Alarm
0 ºC
Coolant Temp High Shutdown
0 ºC
Start Delay Off Load
0 h 0 m 0 s
Start Delay On Load
0 h 0 m 0 s
Start Delay Telemetry
0 h 0 m 0 s
Pre Heat Temp
0 ºC
Pre Heat Timer
0 h 0 m 0 s
Post Heat Temp
0 ºC
Post Heat Timer
0 h 0 m 0 s
Cranking
0 m 0 s
Cranking Rest
0 m 0 s
Safety On Delay
0 m 0 s
Smoke Limiting
0 m 0 s
Smoke Limiting Off
0 m 0 s
Warming
0 h 0 m 0 s
Cooling
0 h 0 m 0 s
Under Speed Shutdown
Active / Inactive
Under Speed Shutdown
0 RPM
Under Speed Warning
Active / Inactive
Under Speed Warning
0 RPM
Over Speed Warning
Active / Inactive
Over Speed Warning
0 RPM
Over Speed Shutdown
0 RPM
Overspeed Overshoot
0 m 0 s
Overspeed Overshoot
0 %
Fail To Stop Delay
0 m 0 s
Battery Under Voltage Warning
Active / Inactive
Battery Under Voltage Warning Delay 0 h 0 m 0 s
Battery Under Voltage Warning
0.0 V
Battery Over Voltage Warning
Active / Inactive
Battery Over Voltage Warning Delay
0 h 0 m 0 s
Battery Over Voltage Warning
0.0 V
Charge Alternator Failure Warning
Active / Inactive
Charge Alternator Failure Warning
0.0 V
Charge Alternator Warning Delay
0 h 0 m 0 s
Charge Alternator Failure Shutdown
Active / Inactive
Charge Alternator Failure Shutdown
0.0 V
Charge Alternator Shutdown Delay
0 h 0 m 0 s
Droop
Active / Inactive
Droop
0 %
Fuel Usage Running Rate
0 %
Fuel Usage Stopped Rate
0 %
DPF Auto Regen Inhibit
Active / Inactive
Specific Gravity
0.80 to 1.00
CAN Termination
Active / Inactive
Generator
Under Voltage Shutdown
0 V
Under Voltage Pre-Alarm
0 V
Loading Voltage
0 V
Nominal Voltage
0 V
Over Voltage Pre-Alarm
0 V
Over Voltage Shutdown
0 V
Under Frequency Shutdown
0.0 Hz
Under Frequency Pre-Alarm
0.0 Hz
Loading Frequency
0.0 Hz
Nominal frequency
0.0 Hz
Over Frequency Pre-Alarm
0.0 Hz
MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED)
Section
Parameter As Shown On Display
Values
Generator
Over Frequency Pre-Alarm
0.0 Hz
(Continued) Over Frequency Shutdown
0.0 Hz
Full Load Rating
0 A
kW Overload Trip
0 %
Delayed Over Current
Active / Inactive
Gen Over Current Trip
0 %
AC System
3 Phase, 4 Wire
CT Primary
0 A
CT Secondary
0 A
Short Circuit Trip
0 %
Earth CT Primary
0 A
Earth Fault Trip
Active / Inactive
Earth Fault Trip
0 %
Transient Delay
0.0 s
Gen Reverse Power Delay
0.0 s
Full kW Rating
0 kW
Full kVAr Rating
0 kvar
Ramp Up Rate
0 %
Ramp Down Rate
0 %
Load Level For More Sets
0 %
Load Level For Less Sets
0 %
Load Demand Priority
1
Gen Reverse Power Trip
0 kW
Insufficient Capacity Delay
0 m 0 s
None / Indication / Warning /
Insufficient Capacity Action
Shutdown / Electrical Trip
None / VAr Share / VAr Fixed
Reactive Load CTL Mode
Export
Load Parallel Power
0 kW
Load Power Factor
0 %
Enable MSC Compatibility
Active / Inactive
Timers
LCD Page Timer
0 h 0 m 0 s
Scroll Delay
0 h 0 m 0 s
Engine Pre Heat Timer
0 h 0 m 0 s
Engine Post Heat Timer
0 h 0 m 0 s
Engine Cranking
0 m 0 s
Engine Cranking Rest
0 m 0 s
Engine Safety On Delay
0 m 0 s
Engine Smoke Limiting
0 m 0 s
Engine Smoke Limiting Off
0 m 0 s
Engine Warming
0 h 0 m 0 s
Engine Cooling
0 h 0 m 0 s
Engine Overspeed Overshoot
0 m 0 s
Engine Fail To Stop Delay
0 m 0 s
Battery Under Voltage Warning Delay 0 h 0 m 0 s
Battery Over Voltage Warning Delay
0 h 0 m 0 s
Return Delay
0 h 0 m 0 s
Generator Transient Delay
0 s
Schedule
Schedule
Active / Inactive
Schedule Bank 1 Period
Weekly / Monthly,
On Load / Off Load / Auto Start
Press
Inhibit, Week, Start Time, Run Time
or down when selecting the
and Day. Selection (1 to 8)
different parameters.
Schedule Bank 2 Period
Weekly / Monthly,
On Load / Off Load / Auto Start
Press
Inhibit, Week, Start Time, Run Time
or down when selecting the
and Day. Selection (1 to 8)
different parameters.

DIMENSIONS AND MOUNTING

Parameter
Specification
Dimensions
245 mm X 184 mm X 51 mm (9.6" X 7.2" X 2.0")
Panel Cutout
220 mm X 160 mm (8.7" X 6.3")
Weight
0.98 kg (2.16 lb)
Operating Temperature
-40 ºC to +70 ºC (-40 ºF to +158 ºF)
Storage Temperature
-40 ºC to +80 ºC (-40 ºF to +176 ºF)
ACCESSING THE 'RUNNING' CONFIGURATION EDITOR
The 'Running' Configuration Editor is enterable without stopping the engine. All
protections remain active whilst using the 'Running' Configuration Editor.
Press and hold the

RUNNING CONFIGURATION EDITOR PARAMETERS

Power Cycle After Exit
Section
Parameter As Shown On Display
Power Cycle After Exit
Display
Contrast
Language
Load Demand Priority
)
Commissioning Screens
Override Starting Alarms
Voltage Adjust
(manual mode only, breaker open)
Frequency Adjust
(manual mode only, breaker open)
Mains Decoupling Test Mode
Engine
Governor Gain
Frequency Adjust Offset
DPF Auto Regen Inhibit
DPF Manual Regen
Power
Power Control Mode
Levels
kVAr Control Mode
Load Parallel Power
In Mains Parallel Mode
Load Parallel kVAr
In Mains Parallel Mode
Load Parallel PF
REQUIREMENTS FOR UL CERTIFICATION
WARNING!: More than one live circuit exists, see diagram overleaf for further
information.
Specification
Screw Terminal
Tightening Torque
Conductors
to begin editing then up
Current Inputs
Communication
to begin editing then up
Circuits
DC Output Pilot Duty
Mounting
Operating
Temperature
(Tick) button to enter and exit the running editor.
Values
0 %
English, Other
1
Active / Inactive
Active / Inactive
0 %
0 %
Active / Inactive
0.0
0.0 Hz
Active / Inactive
Active / Inactive
Const Power / Frequency-Power /
Voltage-Power
Const Power Factor / Voltage-
Reactive Power / Power-Power
Factor / Const Reactive Power
0 %
0 %
0.00 pf
Description
• 4.5 lb-in (0.5 Nm)
• Terminals suitable for connection of conductor size 13 AWG
to 20 AWG (0.5 mm² to 2.5 mm²).
• Conductor protection must be provided in accordance with
NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the
engine starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit
conductors shall be separated and secured to maintain at
least ¼" (6 mm) separation from the generator and mains
connected circuit conductors unless all conductors are rated
600 V or greater.
• Must be connected through UL Listed or Recognized isolating
current transformers with the secondary rating of 5 A max.
• Must be connected to communication circuits of UL Listed
equipment
• 0.5 A
• Suitable for flat surface mounting in Type 1 Enclosure Type
rating with surrounding air temperature -22 ºF to +122 ºF (-30
ºC to +50 ºC)
• Suitable for pollution degree 3 environments when voltage
sensing inputs do not exceed 300 V. When used to monitor
voltages over 300 V device to be installed in an unventilated
or filtered ventilation enclosure to maintain a pollution degree
2 environment.
• -22 ºF to +122 ºF (-30 ºC to +50 ºC)