DuctSox U-Track Руководство по установке - Страница 8
Просмотреть онлайн или скачать pdf Руководство по установке для Промышленное оборудование DuctSox U-Track. DuctSox U-Track 16 страниц.
Step 3 – 2 Row Style
Determine placement of track (both track path and elevation). The bottom of the U-Track must be mounted
"A" inches apart and "B" inches below the 12:00 location of the DuctSox (match this up to the chart and
the drawing.) Track supports are spaced between 5 to 8 ft (1524 to 2440mm) apart with a maximum of 8
ft (2440mm). Additional Track Supports must also be mounted at both ends of continuous track runs for
stabilization (or as an alternative, the track can be secured by mounting the ends with threaded rod). The
track support cable will need to be mounted at angles away from the sides of the track along with angled
cables in-line with the track. See image below.
Diameter
(inches)
A
12
10.83
14
12.56
16
14.29
18
16.02
20
17.75
22
19.49
24
21.22
26
22.95
28
24.68
30
26.41
32
28.15
34
29.88
36
31.61
38
33.34
40
35.07
42
36.81
44
38.54
46
40.27
48
42.00
50
43.73
52
45.47
54
47.20
56
48.93
58
50.66
60
52.39
62
54.13
64
55.86
66
57.59
68
59.32
70
61.05
72
62.79
74
64.52
76
66.25
78
67.98
80
69.72
82
71.45
84
73.18
8
Diameter
B
(mm)
1.63
305
2.13
356
2.63
406
3.13
457
3.63
508
4.13
559
4.63
610
5.13
660
5.63
711
6.13
762
6.63
813
7.13
864
7.63
914
8.13
965
8.63
1016
9.13
1067
9.63
1118
10.13
1168
10.63
1219
11.13
1270
11.63
1321
12.13
1372
12.63
1422
13.13
1473
13.63
1524
14.13
1575
14.63
1626
15.13
1676
15.63
1727
16.13
1778
16.63
1829
17.13
1880
17.63
1930
18.13
1981
18.63
2032
19.13
2083
19.63
2134
A
B
275
41
319
54
363
67
407
79
451
92
495
105
539
117
583
130
627
143
671
156
715
168
759
181
803
194
847
206
891
219
935
232
979
244
1023
257
1067
270
1111
283
1155
295
1199
308
1243
321
1287
333
1331
346
1375
359
1419
371
1463
384
1507
397
1551
410
1595
422
1639
435
1683
448
1727
460
1771
473
1815
486
1859
498
A
B
Installation Guide: U-Track