Dungs VPM-LC Инструкции по эксплуатации и сборке - Страница 13

Просмотреть онлайн или скачать pdf Инструкции по эксплуатации и сборке для Контроллер Dungs VPM-LC. Dungs VPM-LC 18 страниц. Parameter settings and error codes of the control unit line check for valve proving systems

Fehlerübersicht
Error overview
Panoramica errori
Tableau récapitulatif d'erreurs
VPM-LC
0x40 - 0x55
0x56
0x57 - 0x61
Fehlerübersicht
Error overview
Panoramica errori
Tableau récapitulatif d'erreurs
VPM-LC
0xA0
0xA1 - 0xA3
0xA4
0xA4
0xA5
0xA6 - 0xAD
0xAE
0xB0
0xB1 - 0xBA
0xBB
0xBC - 0xC1
0xC2
0xC3
0xC4
0xC5
13 ... 18
Fehlerbeschreibung / Error description /Description des erreurs / Descrizione errore
Reserviert / Reserved / Réservé / Riservato
0
X
FEHLER_WECHSELEINGAENGE_UEBERWACHUNG (StringID 1069)
Reserviert / Reserved / Réservé / Riservato
Fehlerbeschreibung / Error description /Description des erreurs / Descrizione errore
0
X
FEHLER_STATEDAUER_ZU_LANG
Reserviert / Reserved / Réservé / Riservato
0
FEHLER_SICHERHEITSKETTE_OFFEN
Mögliche Fehlerur-
sache:
a) Die Sicherheitskette
wurde geöffnet bzw. ist
nicht geschlossen.
b) Die Adern der
Sicherheitskette sind
unterbrochen.
Frei / Not used / Libre / Non usato
0
X
FEHLER_RUECKMELDUNG_V1_FALSCH
0
X
FEHLER_RUECKMELDUNG_V2_FALSCH
Reserviert / Reserved / Réservé / Riservato
0
FEHLER_VPS_V1_UNDICHT
Das Ventil V1 ist undi-
cht, detektiert über den
Eingang GDW-NO, LED
V1 rot ist ein
0
X
FEHLER_TESTKREISERWEITERUNG
Reserviert / Reserved / Réservé / Riservato
0
X
FEHLER_WD_RUECKMELDUNG_FALSCH
Reserviert / Reserved / Réservé / Riservato
0
X
FEHLER_RUECKMELDUNG_FREIGABE_FALSCH
0
X
FEHLER_RUECKMELDUNG_LGV_FALSCH
0
X
FEHLER_RUECKMELDUNG_LGV2_FALSCH
5
FEHLER_V1IN_FALSCH
Ein angeschlossener
Feuerungsautomat bzw.
SPS öffnet das Ventil V1
in einem unerwarteten
Zustand
Achtung: Ausgabe Fehlerbeschreibung MPA-Vision nur in D/GB/I verfügbar.
Attention: Output error description MPA-Vision only available in D/GB/I.
Attention: Édition de la description des erreurs MPA Vision uniquement
disponible en allemand/anglais/italien.
Attenzione: L'emissione della descrizione dell'errore MPA-Vision è disponibile
solo in tedesco/inglese/italiano.
Achtung: Ausgabe Fehlerbeschreibung MPA-Vision nur in D/GB/I verfügbar.
Attention: Output error description MPA-Vision only available in D/GB/I.
Attention: Édition de la description des erreurs MPA Vision uniquement disponible en
allemand/anglais/italien.
Attenzione: L'emissione della descrizione dell'errore MPA-Vision è disponibile solo in
tedesco/inglese/italiano.
Possible cause of
the error:
a) The safety chain
has been opened or is
not closed.
b) The wires of the
safety chain are inter-
rupted.
Valve V1 is leaking,
detects via the input
GDW-NO, LED V1 red
is on
A connected automat-
ic burner control or
PLC opens the valve
V1 in an unexpected
state.
Cause possible
Possibile causa
de l'erreur :
dell'errore:
a) La chaîne de sécurité
a) La catena di
a été ouverte ou n'est
sicurezza è stata
pas fermée.
aperta oppure non
b) Les brins de la chaîne
è chiusa.
de sécurité sont inter-
b) I conduttori della
rompus.
catena di sicurezza
sono interrotti.
La vanne V1 n'est pas
La valvola V1 non
étanche, détecté par
è ermetica, rilevato
l'entrée GDW-NO, DEL
nell'entrata GDW-
V1 rouge est allumée
NO, LED V1 rosso
è illuminato
Un système de com-
Un sistema automa-
mande automatique de
tico per bruciatori
brûleurs connecté ou
collegato o il PLC
l'API ouvre la vanne V1
apre la valvola V1
se trouvant dans un
in uno stato non
état inattendu
previsto