Operation manual RCWC-04D11
Alarms
Compressor high pressure
The pressure of the operating compressor is two high, the pressure
protection switch compressor is triggered
Lack of cooling, clogged condenser, high temperature of the
cooling water
The unit is overfilled with refrigerant
Manual reset (unmount the cap of the pressure
o
protection switch compressor, green reset button)
Compressor low pressure
The pressure of the operating compressor is too low, the pressure
protection switch compressor is triggered
Insufficient refrigerant
Clogged filter dehydrator
Lack of blowing of the evaporator
Automatic reset - pressure protection switch
o
compressor
Compressor high temperature
The temperature of the operating compressor engine is high
Clogged filter
Insufficient refrigerant
Damaged high temperature module (located in the
compressor electrical box)
Damaged refrigerant injection system
Damaged TEX valves of the evaporators
Automatic reset - after power interruption
Compressor overload
The working current of the operating compressor is high
High pressure
Unsuitable power supply
Damaged compressor
Manual reset - motor protection
o
Cooling water no flow
Lack of water flow through the operating condenser
The water pump is not working
Damaged water regulation valve
Closed valves
OM-RCWC-04D11
2014
18