ADEMCO Counterforce CFV15PCN Руководство по программированию - Страница 3
Просмотреть онлайн или скачать pdf Руководство по программированию для Система безопасности ADEMCO Counterforce CFV15PCN. ADEMCO Counterforce CFV15PCN 16 страниц.
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Field
Function
∗
∗
SYSTEM SETUP (
20–
29)
∗
20
DEALER INSTALLER CODE
∗
21
QUICK ARM ENABLE
∗
22
RF JAM OPTION
∗
23
QUICK (FORCED) BYPASS
∗
24
RF HOUSE ID CODE
∗
26
CHIME BY ZONE
∗
27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
∗
28
ACCESS CODE FOR
PHONE MODULE
∗
29
LONG RANGE RADIO OUTPUT
ZONE SOUNDS AND TIMING (
∗
31
SINGLE ALARM SOUNDING per ZONE
∗
32
FIRE ALARM SOUNDER TIMEOUT
∗
33
ALARM SOUNDER (BELL) TIMEOUT
∗
34
EXIT DELAY
∗
35
ENTRY DELAY #1 (zone type 01)
∗
36
ENTRY DELAY #2 (zone type 02)
∗
37
AUDIBLE EXIT WARNING
∗
38
CONFIRMATION OF ARMING DING
∗
39
POWER UP IN PREVIOUS STATE
DIALER PROGRAMMING (
Do not fill unused spaces. Enter 0–9; #+11 for '
∗
field by pressing [
]. The next data field number is displayed.
∗
40
PABX ACCESS CODE
∗
41
PRIMARY PHONE No.
∗
42
SECOND PHONE No.
PROGRAMMING FORM
Data Entries
|
|
|
∗
∗
31 –
39)
|
|
|
∗
∗
40 –
42)
∗
'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the
|
used, enter "∗ (#+11) 70" plus "# + 13" (pause).
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Enter up to 20 digits. To clear entries, press
NOTE: These phone number fields cannot be edited by the Dealer Installer Code after the panel is locked.
Programmable Values
4 digits, 0–9
|
|
[4112]
Can perform all system functions except, after the panel
is locked, cannot edit the reporting phone numbers
(fields *41, *42); panel is locked after initial upload.
0 = no; 1 = yes
[1]
0 = no RF Jam detection; 1 = send RF Jam report
[0]
UL: must be 1 if wireless devices are used
0 = no quick bypass UL: must be "0"
[0]
1 = allow quick bypass (code + [6] + [#] )
00 = disable all wireless keypad usage
[0,0]
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
[0]
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
[0]
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
[00]
∗
for "
", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
0 = disable; 1 = enable
[0]
0 = no UL: must be "0"; 1 = yes
[0]
0 = sounder stops at timeout;
[1]
1 = no sounder timeout UL: must be "1" for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
[1]
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
00 - 96 = 0 - 96 secs; 97 = 120 secs
[60]
SIA Installations: minimum exit delay is 45 seconds
UL: see inst. instr. for requirements.
00 - 96 = 0 - 96 seconds
[30]
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
For UL Residential Burglary Alarm installations, must be set
for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm,
total entry delay may not exceed 45 seconds.
See *35 Entry Delay 1 above for entries.
[30]
0 = no; 1 = yes
[1]
SIA Installations: must be enabled (enter 1)
0 = no; 1 = yes (wired keypads and RF)
[0]
2 = yes, RF only
UL: must be "1" for UL Commercial Burglar Alarm inst.
0 = no; 1 = yes UL: must be "1"
[1]
Enter up to 6 digits. To clear entries, press
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
∗
∗
∗
41
or
42
– 3 –
SIA Installations:
minimum entry delay is
30 seconds
∗
40
|
|
|
|
|
|
∗
respectively .
∗
. If call waiting