: digital input signal from an external contactor/breaker to the meter, this is
Pulse
normally read by a building management system via Modbus.
: The alarm is seen as a bell on the display and can be programmed to
ALARM
Over Voltage, Under Voltage, Over Current, the Unbalance of currents and Voltage
alarms. Opens and closes a relay for a set time.
Programming the switching configuration on DO1 and DO2. The cursor will be over
the "level" indicator, to alter this to pulse or alarm press the key with the arrow to
the right
this will scroll through the options. When you have selected your
option, press the key with the arrow facing down, this will move the cursor to the
four digits on the left. "0000" this is the time the relay will stay open or closed and is
based in milli seconds. Use the key with the arrow facing right
numbers. Use the key with the arrow facing down
When you have reached the last position in the digits on line 1 press the key with
the arrow facing right
this will move the cursor down to the 2nd line. This line
represents Digital output 2. Repeat above to program this output.
When you have programmed the digital outputs press Return
on the screen with "YES" and"NO"
left
so the "YES" is highlighted. Press return
Press Menu.
: This is used for setting the value you want
ALARM
the alarm to be activated.
You will see on the screen 5 options where you
can input values to set an alarm. When this value
has been reached a relay will close or open.
V
> 000.0
Over Voltage
V
< 000.0
Under Voltage
I
> 0.000
Over Current
Vuf
< 000.0
Unbalance of Current
Iuf
< 000.0
Unbalance of Voltage
The cursor will be positioned on the first "0" on the top line (Over voltage) press the
key with the arrow facing right
down to
move the cursor one step to the right. Repeat until you have
completed your programming.
Repeat above to program the other values as listed on the display.
18
8
to increment the
to move the cursor to the right.
. A box will appear
press the cursor with the arrow facing
YES
NO
.
ALARM
U
< 000.0
U
> 000.0
I
> 0.000
VUF > 000.0
IUF > 000.0
to increment or press key with arrow facing
When you have programmed the alarm outputs press return
on the screen with "YES" and"NO"
left
so the "YES" is highlighted. Press return
Press Menu.
Press the key with the arrow facing down
highlighted "OTHERS". Press return
OTHERS
: This is used for resetting registers back to zero.
You will see on the display a small menu.
CLR.E:
OFF YES - resets the energy
registers to zero
CLR.S:
OFF YES - resets the time stamps
in the S.O.E.
CLR.MD:
OFF YES - resets the maximum
demand back to zero
BACKLIGHT: OFF YES - turns backlight
permanently on
CONTRAST: 50
This allows adjustment on
the contrast of the display 0-55
You will notice that the cursor has highlighted the "OFF " position on the CLR.E on
the display. To change this to "YES" press return key
"YES" "NO"
. . Move the cursor to "YES" by pressing the key with the arrow
YES
NO
marked on the left
then press return
Repeat above to adjust other options.
Press Menu to return to CONFIG screen.
Press Menu again to return to main menu.
NOTE
:
When in the OFF position, the backlight allows a view time of 40 seconds before
switching off. Continually pressing the return key
will keep on extending the illumination of the display by 40 seconds.
If you switch the backlight permanently ON then please be aware this will shorten the
life of the display.
1
. A box will appear
press the cursor with the arrow facing
YES
NO
.
. This now moves you down and has
.
OTHERS
CLR.E
CLR.S
CLR.MD
BACKLIGHT OFF
CONTRAST
this brings up a box with
this takes you back to "OTHERS" screen.
when you are operating the meter
NO
YES
OFF
45
19