Autonics TMH Series Краткое руководство по эксплуатации - Страница 2
Просмотреть онлайн или скачать pdf Краткое руководство по эксплуатации для Контроллер температуры Autonics TMH Series. Autonics TMH Series 6 страниц. Modular2/4-channel pid temperature controllers with screw connector
• Do not apply excessive power when connecting or disconnecting the connectors of the
product.
• Switch or circuit breaker should be installed nearby users for convenient control.
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature
controller.
• When changing the input sensor, turn off the power first before changing.
After changing the input sensor, modify the value of the corresponding parameter.
• Power supply should be insulated and limited voltage/current or Class 2, SELV power
supply device.
• Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of
line to reduce the effect of external noise.
• Make a required space around the unit for radiation of heat.
For accurate temperature measurement, warm up the unit over 20 min after turning on
the power.
• Mounting multiple devices in any way other than the specified mounting method may
cause heat to build up inside, which will shorten their service life. If there is a possibility
of the ambient temperature rising to a temperature above the specified temperature
range, take steps, such as installing fans, to cool the device. Be sure that the cooling
method in not cooling just the terminal block. If only the terminal block is cooled,
measurement errors may occur.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after
supplying power.
• Do not wire to terminals which are not used.
• Install DIN rail vertically from the ground.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in 'Specifications')
- Altitude max 2,000 m
- Pollution degree 2
- Installation category II
Ordering Information
This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics website.
■ Control module
T
M
H
❶
-
❶ Channel
2: 2 channels
4: 4 channels
❷ Alarm output
2: Alarm output 1/2 (2 channels)
4: Alarm output 1/2/3/4 (2
channels)
N: None (4 channels)
■ Option module
Model
Input
TMHA-42AE
Temperature sensor / Analog input 1 to 4 Transmission output (0/4 - 20 mA) 1 to 4
TMHE-82RE
Digital input 1 to 8
TMHCT-82NE
CT input 1 to 8
■ Communication module
Model
Connection type
TMHC-22LE
RS422, RS485
TMHC-22EE
Ethernet (10BaseT)
Firmware Version and Manual
Additional settings may be required if the firmware version is different between the
connected modules.
Please refer to the user manual and the user manual for communication, and be sure to
follow cautions written in the technical descriptions.
Visit our website (www.autonics.com) to download manuals.
DAQMaster
• DAQMaster is comprehensive device management program. It is available for
parameter setting, monitoring.
• Visit our website (www.autonics.com) to download the user manual and the program.
❷
2
❸
❹
❸ Control output
R: Relay output
S: SSR drive output
C: Selectable current or SSR drive output
❹ Module type
B: Basic module
E: Expansion module
• Since the expansion module is not supplied with
power/comm. terminal. Use it with the basic
module.
Output
Alarm output 1 to 8
-
Protocol
Modbus RTU, PLC Ladderless
communication
Modbus TCP
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
■ Side
85
Specifications
■ Control module
Model
TMH2
No. of channels
2 channels
Sampling period
50 ms (2 channels or 4 channels synchronous sampling)
Input specification
Thermocouple, RTD, Analog (refer to 'Input Specification')
• 0.0 - 50.0A (primary current measurement range)
CT input
• CT ratio: 1/1,000, • Measurement accuracy: ±5% F.S. ±1 digit
• Connect input
ON: ≤ 1 kΩ, OFF: ≥ 100 kΩ
• Solid state input
Digital input
Residual voltage: ≤ 0.9 V,
Leakage current: ≤ 0.5 mA
• Outflow current: ≈ 0.3 mA per input
Control type
Heating, cooling, heating & cooling: ON/OFF, P, PI, PD, PID control
• Relay: 250 VACᜠ 3 A 1a
mechanical life cycle: ≥ 10,000,000 operations,
Control output
electrical life cycle: ≥ 100,000 operations
• SSR: 12 VDCᜡ ±3 V, ≤ 20 mA
• Current
: DC 4 - 20 mA or DC 0 - 20 mA (Load: ≤ 500 Ω)
01)
250 VACᜠ 3 A 1a
Mechanical life cycle: ≥ 10,000,000
Alarm output
Electrical life cycle: ≥ 100,000 operations
Communication
Modbus RTU
• Thermocouple / RTD: 1 to 100 (0.1 to 100) ℃/℉
Hysteresis
• Analog: 1 to 100 digit
Proportional band
• Thermocouple / RTD: 1 to 999 (0.1 to 999.9) ℃/℉
(P)
• Analog: 0.1 to 999.9 digit
Integral time (I)
0 to 9,999 sec
Derivative time (D)
0 to 9,999 sec
• Relay output, SSR drive output: 0.1 to 120.0 sec
Control period (T)
• Selectable current or SSR drive output: 1.0 to 120.0 sec
Manual reset
0 to 100 (0.0 to 100.0) %
Double insulation or reinforced insulation (mark: ▱, dielectric strength
Insulation type
between the measuring input part and the power part: 1 kV)
Unit weight
• Basic module: ≈ 178 g (≈ 251 g)
(packaged)
• Expansion module: ≈ 173 g (≈ 246 g)
01) When the control output is set to the current output, the heater current value monitoring function through the CT
input terminals is not available.
■ Option module
Model
TMHA-42AE
No. of channels
4 channels
Sampling period
50 ms (4 channels synchronous sampling)
Input specification
Thermocouple, RTD, analog (refer to 'Input Specification')
Transmission output DC 4 - 20 mA or DC 0 - 20 mA (Load: ≤ 500 Ω)
Communication
Modbus RTU
Double insulation or reinforced insulation (mark: ▱, dielectric strength
Insulation type
between the measuring input part and the power part: 1 kV)
Unit weight
≈ 161 g (≈ 234 g)
(packaged)
Model
TMHE-82RE
No. of channels
8 points
- Digital input
• Connect input
ON: ≤ 1 kΩ, OFF: ≥ 100 kΩ
Input specification
• Solid state input
Residual voltage: ≤ 0.9 V,
Leakage current: ≤ 0.5 mA
• Outflow current: ≈ 0.3 mA per input
250 VACᜠ 3 A 1a,
• Mechanical life cycle:
Alarm output
≤ 10,000,000 operations
• Electrical life cycle:
≤ 100,000 operations
• Comm. terminal: RS485, • PC loader: TTL • Protocol: Modbus RTU,
Communication
Double insulation or reinforced
insulation (mark: ▱, dielectric
Insulation type
strength between the measuring
input part and the power part: 1 kV)
Unit weight
≈ 166 g (≈ 239 g)
(packaged)
■ Front
■ Inside
9
12
30
2-Ø 4.3
TMH4
4 channels
-
-
operations
TMHCT-82NE
8 points
- CT input
• 0.0-50.0 A (primary current
measurement range)
• CT ratio: 1/1,000
• Measurement accuracy: ±5%
F.S. ±1 digit
-
-
≈ 148 g (≈ 221 g)