Readjustment of the force via the digital potentiometer
With the help of the digital potentiometer (preset value: middle position) the force at the door border can be adjusted to a
certain degree. Press button of the digital potentiometer for 2-3sec
set value is shown. By pressing the button the value of power is increased, this is shown by LEDs lighting up. The power
value is increased clockwise. After reaching the maximal value, the digital potentiometer jumps back to minimum with the
next pressing of the button. After approx. 2 min. the digital potentiometer switches into a non-active mode, thereby the last
set value will be stored. In the factory set up mode and after programming of path and force the digital potentiometer is al-
ways set in the middle position! After adjusting the digital potentiometer check the cut-off force.
The force values according to the norms may not be exceeded!
ATTENTION:
Status display / Error display:
indication red
LED (in normal
operation)
continuous light
emergency-stop has been activated or
jumper is missing on "NOT" terminal
1x flashing
safety devices (photo cells or optoelektronic
safety barrier) have been actuated resp. are
not correctly activated
2x flashing
force cut-off / overload
3x flashing
sensor error, the Hall-sensor cable is not or
not correctly connected or the motor cables
are interchanged
4x flashing
error on the control board
5x flashing
motor error, motor cables not connected
6x flashing
EEPROM-data error
indication green
LED
control unit is ready for operation
on
no power supply
off
*
keep mains plug for 1min unplugged
S 201
potential cause
display of operation status
untill
all Poti-LEDs light up. Then release the button, the
eliminate the interruption, a start command will
start the operator again
eliminate the interruption, a start command will
start the operator again
try to start the operator again, otherwise repeat
the path and force setting
connect the Hall-sensor-cable and motor ca-
bles properly, disconnect and reconnect the
*
mains plug
, afterwards repeat the path and
force setting
will work after disconnecting and reconnecting
the mains plug
board
connect motor cables, then disconnect and
reconnect the mains plug
will work after disconnecting and reconnecting
the mains plug
control board
check conduction line and fuse
13
trouble shooting
*
, otherwise replace control
*
*
, if error occurs again replace
trouble shooting
01-07