The lower right corner of
Figure 4-1
shows the positioning of the rack ears and screws. Note that the rack
ears supplied with the S2410 have a hole in the middle to accommodate the vent in the S2410.
Figure 4-1. Attaching Rack Ears to Switch

Two-Post Rack Mounting

Ensure that there is adequate clearance surrounding the rack to permit access and airflow (see
Chapter ,
Site Preparation, on page
11).
If you are installing two S2410 systems side-by-side, position the two S2410 chassis at least 5 inches
(12.7 cm) apart to permit proper airflow.
Position the S2410 chassis in the rack (attach the rack ears first, using only the supplied screws; see
Attaching the Rack Ears on page
15). Secure the chassis with two screws through each bracket (rack ear)
and onto the front rack post, as shown in
Figure
4-2.
16
|
Installing the S2410