393803‐2 Startup procedure for EnSy AHU units
Press control button 3 (+) once and you will have 1000 in display. 
Press control button 4 (enter) four times and OK will show up in 
display.  
Press control button 3 (OK) to get into 4.5.1 Setup.  
Press control button 3 nine times to get to Display number.  
Press control button 4 once to get into 4.5.1.10 Display number.  
Press control button 3 (+) once until it shows Display 2.  
Press control button 1 (Return) three times to get back to start 
up menu. 
 
 
3. How to control the fan speed. 
 
Set the unit to NORM fan speed after installation. 
 
Press control button 2 or 3 (under – and +) to get back to NORM fan speed. 
Press control button 1 (Return) once to get back to start up menu.
We reserve the right to change technical data without notice     http://www.ensy.no 
REV:0_08.09.2016. KJK 
The fan speed is set to OFF 0% from factory. 
 
Press control button 1 once to get into 4.1 Fan speed.  
There are different values on MIN, NORM and MAX 
depending on the unit type. Factory settings you can find 
in «User manuals and Installation Guide» under menu 
4.5.1.3. Fan control. 
 
Press control button 3 (+) to test the unit on MIN speed.  
(It is the value for supply air fan that shows in display) 
 
If adjusted. What is new value after installation? 
Supp: _____%       Extr: _____% 
 
 
 
Press control button 3 (+) to test the unit on NORM 
speed. (It is the value for supply air fan that shows in 
display) 
 
If adjusted. What is new value after installation? 
Supp: _____%       Extr: _____% 
 
 
 
Press control button 3 (+) to test the unit on MAX speed. 
(It is the value for supply air fan that shows in display) 
 
If adjusted. What is new value after installation? 
Supp: _____%       Extr: _____% 
 
 
 
Page 3