393803‐2 Startup procedure for EnSy AHU units
4. How to adjust % for MIN, NORM and MAX to get balanced ventilation. 
After adjustments use control button 1 (Return) three times to get back to the start up menu. 
 
Which % intervals are there on the different operating steps?
OFF = 0% 
MIN = 30 ‐ 49% 
NORM = 50 ‐ 79% 
MAX = 80 ‐ 100%
We reserve the right to change technical data without notice     http://www.ensy.no 
REV:0_08.09.2016. KJK 
 
 
 
 
Press control button 4 once to get into 4 Preferences. 
 
 
 
 
Press control button 3 four times to get to Setup. 
 
 
 
Press (Enter) control button 4 to get into 4.5 PIN code 
menu. 
 
 
Press control button 3 (+) once and you will have 1000 in 
display. 
 
Press control button 4 (enter) four times and OK will show 
up in display.  
 
 
 
 
Press control button 3 (OK) to get into 4.5.1 Setup.  
 
 
Press control button 3 twice to get to Fan control.  
 
Press control button 4 (enter) to get into 4.5.1.3 Fan 
control menu. 
 
There are different values on Min, Normal and Max 
depending on the unit type. Factory settings you can find in 
«User manuals and Installation Guide» under menu 4.5.1.3. 
If you need to do adjustments here to get balanced 
ventilation then please fill in the new settings on previous 
page. 
Change values with control buttons 2 (‐) or 3 (+). 
Move between Supp. and Extr. with control button 4. 
 