Dell S4100-ON Series Руководство по установке - Страница 17

Просмотреть онлайн или скачать pdf Руководство по установке для Переключатель Dell S4100-ON Series. Dell S4100-ON Series 48 страниц.
Также для Dell S4100-ON Series: Руководство по установке (47 страниц), Руководство по настройке (21 страниц), Руководство по установке (49 страниц)

Dell S4100-ON Series Руководство по установке
The S4100–ON Series (S4128F-ON, S4148F-ON, and S4148FE-ON) is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
Network telecommunication facilities
Data centers
Other locations where the National Electric Code (NEC) applies
For more information about the S4100–ON Series specifications, see Specifications.
NOTE:
Install the switch into a rack or cabinet before installing any optional components.
Topics:

Site selection

Cabinet placement
Rack mounting
Switch ground
Fans and airflow
Power
Storing components
Site selection
Install Dell EMC equipment in restricted access areas.
A restricted access area is one where service personnel can only gain access using a special tool, lock, key, or other means of security. The
authority responsible for the location controls access to the restricted area.
Ensure that the area where you install switch meets the following safety requirements:
Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local electrical
codes.
Environmental—switch location—continuous temperature range is from 50° to 104°F (from 5° to 40°C).
Operating humidity is from 5 to 85 percent noncondensing, continuous.
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct sunlight.
Away from sources of severe electromagnetic noise.
Inside the restricted access area, position in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for
proper ventilation and access.
Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA 75.
For more information about switch storage and environmental temperatures, see Specifications.

Site preparations

Site preparations
3
17