Dell S4248FB-ON Руководство по настройке - Страница 16

Просмотреть онлайн или скачать pdf Руководство по настройке для Переключатель Dell S4248FB-ON. Dell S4248FB-ON 29 страниц. S4200-on series
Также для Dell S4248FB-ON: Руководство по установке (47 страниц)

Dell S4248FB-ON Руководство по настройке
To remove the two screws from each front flange ear on the switch side of the rail and
remove each latch casting, use a Torx screwdriver. Retain the latch castings for future
rack requirements. It is not necessary to remove the back flange castings.
Figure 4. Two-post flush-mount installation
2
Attach one rail to the front post flange with two user-supplied screws, item 2.
3
Slide the plunger bracket forward against the vertical post and secure the plunger
bracket to the post flange with two user-supplied screws, item 3.
4
Repeat this procedure for the second rail.
16
S5048F-ON switch installation