Water Coming from the Heat Pump..
Is it a leak or just condensation from normal operation?
Here's how to find out.
Test the water draining out the heater base for the presence of the sanitizer
being used in the pool or spa. Using a water test kit, or a test strip, check a
sample of the water for chlorine or bromine. If the sample tests positive for
sanitizer, call Aquatherm for service at: 239-482-0606. If the test is negative,
the water is probably harmless condensation.
Or, as an alternate method, shut the heat pump off, leaving the circulation
pump running. Within a few hours, there should be a marked reduction in
the amount of water seen around the bottom of the heat pump. If the water
appears to be drying up, the water is probably harmless condensation, indica-
tive of normal operation.
NOTE: The water test method will not be effective if an ionizer or ozone gen-
erator is being used to produce the sanitizing agent.
CAUTION! If after testing, a water leak is suspected, immediately shut OFF
the water pump and contact Aquatherm Customer Support: 239-482-0606.
SAFETY INFORMATION
Used and maintained properly, your heat pump will provide years of safe and
economical service. However, as with any mechanical or electrical device,
to get the most from your heat pump-while insuring personal safety for you
and others-certain operational and maintenance factors must be observed.
Except for a few minor owner-capable maintenance items (explained later in
this manual), repair and service of your heat pump must be performed only by
licensed service personnel. If you suspect your heat pump is not performing
properly, refer to the Troubleshooting section in this manual to determine if
service is required. Your installer can be one source of service, or you can call
Aquatherm at (239) 482-0606 or 888-297-3826. For questions concerning
installation, modifications, operation, service and upkeep, please contact your
installer or Aquatherm Customer Support.
WARRANTY MAY BE VOIDED IF THE HEATER HAS BEEN
USED, MAINTAINED, OR REPAIRED IMPROPERLY.
In addition to voiding the manufacturer's warranty, unapproved installation
methods, nonstandard modifications, poor or incorrect maintenance, service
by unqualified personnel, or improper use of the heater may result in personal
injury and/or property damage. For personal safety, and to avoid damage to
equipment, follow all safety instructions displayed on the heat pump and
within this manual.
15
.
CONTENTS
Model/Serial # ....................................................................Cover
Heat Pump Options ....................................................................1
How A Heat Pump Works ..........................................................1
Heating Quick Start & Stop ................................................. 2 - 3
Heater Controls ..........................................................................4
Operational & Programming Codes ...........................................5
Operational & Maintenance Recommendations ........................6
Maintenance & Operation .................................................... 7 - 8
Proper Water Flow
Water Chemistry Standards
Pool & Spa Refinishing
Irrigation and Storm Run-Off
Proper Clearances
Heating Tips ...............................................................................9
Seasonal Use & Shut Down .....................................................10
Freeze Protection .....................................................................10
Recommended Maintenance ....................................................11
Troubleshooting ............................................................... 12 - 13
Safety Information ...................................................................13
Aquatherm Contact Information ...............................Back Cover
i