PROGRAMMING INSTRUCTIONS
Please read all 3 steps before programming
1.
Enter a programming function by pressing button the number
of times as the desired function number from the tables below
(e.g., press twice for function 2, time delay).
2.
LED will flash back the selected function's current setting
(e.g., 5 flashes for 10 minute time delay). To change setting,
proceed to step 3 before flash back sequence repeats 3 times.
To exit the current function or to change to a different function,
wait for sequence to repeat 3 times then return to step 1.
3.
Press button the number of times indicated in the particular
function's detailed table for the NEW desired setting (e.g.,
press 3 times for 5 min). As confirmation of setting change,
LED flashes back the NEW setting 3 times before exiting.
FUNCTIONS
Standard
2
Time Delay
3
Idle Time Until Dim
4
100 Hr Burn-In /
Auto Set-Point
5
Ten's Digit of Set-Point
6
One's Digit of Set-Point
7
Sunlight Discount Factor
8
Incremental Set-Point
Adjustment
11 Photocell Mode
12 Dual Tech. (Microphonics
)
TM
1
15 Photocell Dim Range (High)
16 Photocell Dim Range (Low)
21 Photocell Transition Off Time
22 Photocell Transition On Time
23 Occupied Bright Level
24 Unoccupied Dim Level
DETAILED FUNCTION TABLES
2 = Time Delay
1
30 sec
2
2.5 min
3
5.0 min
3 = Idle Time Until Dim
1
30 sec
2
2.5 min
3
5.0 min
4 = 100 Hour Burn-In / Auto Set-Point
1
Disabled*
Options
2
Enabled
P
ADC ADCX
3
Enabled then run Auto-Setpoint
4
Run Auto Set-Point
5
Blink back Set-Point
2
The LED will blink back the ten's digit, then pause, then blink back
the one's digit. For a "0" the LED will blink very rapidly. The sequence
is repeated 3 times.
5 = Ten's Digit of Set-Point
1
10 fc
2
20 fc
3
30 fc
6 = One's Digit of Set-Point
1
1 fc
2
2 fc
3
3 fc
7 = Sunlight Discount Factor
1 x/1***
2 x/2
3 x/3
* DEFAULT SETTING
PDT SENSORS ONLY
1
4
7.5 min
7
15.0 min
5
10.0 min*
8
17.5 min
6
12.5 min
9
20.0 min
4
7
15.0 min 10 Disable
7.5 min*
5
10.0 min
8
17.5 min
6
12.5 min
9
20.0 min
2
4
40 fc
7
200 fc
5
50 fc
8
Disabled*
6
100 fc
10 0 fc**
4
4 fc
7
7 fc
5
5 fc*
8
8 fc
6
6 fc
9
9 fc
4 x/4*
7 x/7
5 x/5
8 x/8
6 x/6
9 x/9
** P, ADC, and ADCX DEFAULT
*** nCM(R)(B)-6 or nCM(R)B-50 UNITS' DEFAULT
8 = Incremental Set-Point Adjustment
1 Decrease 1 fc
11 = Photocell Mode
1 Full On/Off Control*
12 = Dual Technology (Microphonics
1 On*
15 = Photocell Dim Range (High)
1 Min
2 10%
3 20%
16 = Photocell Dim Range (Low)
1 Min
2 10%*
3 20%
21 = Photocell Transition Off Time
1 45 sec
2 2 min
22 = Photocell Transition On Time
1 45 sec*
2 2 min
23 = Occupied Bright Level
10 0 fc
1 10%
2 20%
3 30%
24 = Unoccupied Dim Level
10 x/10
1 10%*
2 20%
3 30%
* DEFAULT SETTING
2 Increase 1 fc
2 Inhibit Only Control
)
TM
2 Off
4 30%
7 60%
10 90%
5 40%
8 70%
11 100%*
6 50%
9 80%
4 30%
7 60%
10 90%
5 40%
8 70%
11 100%
6 50%
9 80%
3 5 min*
5 15 min
7 25 min
4 10 min
6 20 min
3 5 min
5 15 min
7 25 min
4 10 min
6 20 min
4 40%
7 70%
10 100%*
5 50%
8 80%
6 60%
9 90%
4 40%
7 70%
10 100%
5 50%
8 80%
6 60%
9 90%