FUNCTION DEFINITIONS
2 TIME DELAY
The length of time an occupancy sensor will keep the lights on
for after it last detects occupancy.
3 IDLE TIME UNTIL DIM
The length of time after last detected occupancy that a sensor will
reduce lighting to unoccupied dim level.
4 100 HOUR BURN-IN / AUTO SET-POINT
100 HOUR BURN-IN
Overrides relay on and/or dimming output to full bright
(typically for lamp seasoning).
AUTO SET-POINT
Photocell calibration procedure for detecting optimum lighting
control level.
5 TEN'S DIGIT OF SET-POINT
The ten's digit of the target light level that is to be maintained by
the device (in foot-candles).
6 ONE'S DIGIT OF SET-POINT
The one's digit of the target light level that is to be maintained by
the device (in foot-candles).
7 SUNLIGHT DISCOUNT FACTOR
Value used to improve the tracking accuracy of a photocell during
periods of high daylight. Decreasing the value will lower the
controlled level of the lights.
8 INCREMENTAL SET-POINT ADJUSTMENT
Alters the target light level that is to be maintained by the device
(in foot-candles).
11 PHOTOCELL MODE
Indicates a photocell sensor's method of operation. One mode
enables the sensor to turn the lights both on and off, while the
other mode can only inhibit the lights from turning on.
12 DUAL TECHNOLOGY (MICROPHONICS
A second method of occupancy detection that allows the sensor
to hear occupants.
15 PHOTOCELL DIM RANGE (HIGH)
The percentage of the controllable dimming range up to which an
automatic dimming photocell will control.
16 PHOTOCELL DIM RANGE (LOW)
The percentage of the controllable dimming range down to which
an automatic dimming photocell will control.
21 PHOTOCELL TRANSITION OFF TIME
The time period for which a photocell must measure a light level
above the set-point before it will turn the lights off.
22 PHOTOCELL TRANSITION ON TIME
The time period for which a photocell must measure a light level
below the set-point before it will initiate the lights on.
23 OCCUPIED BRIGHT LEVEL
The percentage of the controllable dimming range that a dimming
sensor sets the lights to when occupancy is detected. Setting
is not applicable if photocell is enabled. Note: Adjusting the dim
level using a WallPod changes this setting.
24 UNOCCUPIED DIM LEVEL
The percentage of the controllable dimming range that a dimming
sensor sets the lights to after the idle time until dim timer expires.
Additional settings can be configured
via SensorView software.
)