1.10.5 PAR_Off Delay (s)

Property Datatype: PDT_UNSIGNED_16bit
Datapoint Type: None
Range: [1÷65535]
It defines the waiting time in seconds from the reception of the DPT_Channel X Set ON/OFF = Off message
before switching a channel in the Off status. Default value is 5. The maximum value corresponds to a waiting
of about 18 hours.

1.10.6 PAR_Blink On (s), PAR_Blink Off (s)

Property Datatype: PDT_UNSIGNED_16bit
Datapoint Type: None
Range: [1÷65535]
They define the blinking periods in seconds for Channel status ON and OFF at the reception of the
DPT_Channel X
Set ON/OFF = On message. The ON status will remain for PAR_Blink On (s) seconds while
the OFF for PAR_Blink Off (s) seconds. Default value is 5. The maximum value corresponds to periods of
about 18 hours.

1.10.7 PAR_Upper Threshold, PAR_Lower Threshold

Property Datatype: PDT_UNSIGNED_16bit
Datapoint Type: None
Range: [0÷65535]
They define the upper and lower threshold for channel activation/deactivation based on the
PAR_Comparison method parameter. The gap between the two values defines the switching hysteresis. The
values assigned to the PAR_Upper Threshold and PAR_Lower Threshold parameters must be consistent
following the relationship:

1.10.8 PAR_Comparison method

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷1]
It defines the comparison method used to set the thresholds exceeding direction for the channel activation.
Value 0 (default) indicates the upward direction, i.e. the channel is activated when the value of the input
exceeds PAR_Upper Threshold and is disabled when that value falls below of PAR_Lower Threshold, which
is equal to PAR_Upper Threshold minus the switching hysteresis. Value 1 indicates the downward direction
and the activation/ deactivation of the channel are reversed.

1.10.9 PAR_Stairs Light Time (s)

Property Datatype: PDT_UNSIGNED_16bit
Datapoint Type: None
Range: [1÷65535]
It defines the stairs lighting time in seconds after the reception of the DPT_Channel X
message. The lights timer is reset each time the device gets the message. Default value is 30. The maximum
value corresponds to about 18 hours.

1.10.10 PAR_Enable Logic Function

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷1]
This parameter enables or disables the functions of the channel logical block. Default value 0 means the
functions are disabled, when disabled, all the communication objects related to the logical function are
hidden in the device descriptor, otherwise they appear according to the logical operator set with the
PAR_Logic Operator parameter.
FINDER SpA
PAR_Upper Threshold > PAR_Lower Threshold
Ver. 2018
KNX Actuator 19.6K
Set ON/OFF = Off
14