finder 19 Series Руководство - Страница 15

Просмотреть онлайн или скачать pdf Руководство для Контроллер finder 19 Series. finder 19 Series 17 страниц. Knx actuator

finder 19 Series Руководство

1.10.11 PAR_Logic Operator

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷4]
It selects the type of logical operator when the PAR_Enable Logic Function parameter is set to 1. The
allowable values shown in Table 4.

1.10.12 PAR_Value PORT Locked

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷1]
It selects the value by which the channel will be locked in the logical function PORT.

1.10.13 PAR_Enable Scenes

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷1]
It enables or disables the visualization of the channel scenarios page.

1.10.14 PAR_Value Force Out

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷1]
It is the value of the forcing status with medium priority.

1.11 Detailed description of the parameters of channel scenes configuration page

1.11.1 PAR_Scene Y Number
Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: enumerated
Range: 0÷64
It sets the number of Channel Y scenario. The number appears on the descriptor by an offset of +1, as required
by the official KNX specifications.
1.11.2 PAR_Scene Y Value
Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: enumerated
Range: [0÷1]
It set the channel status expected for the Y scenario. Default value 0 corresponds to the OFF status, while
value 1 corresponds to ON status.
FINDER SpA
Value
0
(default)
1
2
3
4
Y
)
4)
Ver. 2018
PAR_Logic
Operator
AND
OR
XOR
PORT
THRESHOLD
Table 4
KNX Actuator 19.6K
15