Dinel CLS-23 Руководство по эксплуатации - Страница 6

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Аксессуары Dinel CLS-23. Dinel CLS-23 18 страниц. Capacitive level sesors
Также для Dinel CLS-23: Руководство (20 страниц)

Dinel CLS-23 Руководство по эксплуатации
6 .  m
oUnting recommendation
 level sensors can be ed in a vertical horiontal or bevelled position into the shell of the
vessel the storage tan for the ation console in the pit by screwing into the welding ange using
a ing nut or T process connection.
asic application recommendations are mentioned below.
During assembly into the metal tank or the storage tank, it is not necessary to separately ground the
base of the level sensor. In the case of installation in concrete tanks or silos, it is recommended to
install a level sensor on the auxiliary metal construction (console, cap, etc.) and to then connect it
using a permanently dipped metal item or with steel reinforcement in the concrete (armouring).
In the case of the reading of an aggressive medium, we recommend that the producer be consulted.
If the sensors are tted with protective caps at the ends of the electrodes, remove the
caps before commissioning.
d
Fig. 1: Vertical mounting
b
Fig. 2: Bypass measuring tube
 Dinel
CLS 23
or top mounting vertical position it is necessary to eep the
distances from walls and from other sensors.
=
+
c
10
50
k
E Electrode length in mm
ounting in a bypass measuring tube. e recommend to
eep the tube diameter.
=
+
b
40
E Electrode length in mm
E
E
=
+
d
40
40
E
20
All vertically mounted sensors
E
=
+
k
20
20
Applies to: CLS 23_ 20, 21, 30
7