ABB CoriolisMaster FCH400 Series Руководство по конфигурации - Страница 9

Просмотреть онлайн или скачать pdf Руководство по конфигурации для Блок управления ABB CoriolisMaster FCH400 Series. ABB CoriolisMaster FCH400 Series 11 страниц. Hspc module

configure or operate the CoriolisMaster meters, refer to the CoriolisMaster FCB400, FCH400 Operation
Instructions (See
Additional information
Pre-requisites:
The CoriolisMaster is powered.
The CoriolisMaster configuration is complete (Digital Output 41/42 is configured as required).
Use the operator buttons to navigate on the CoriolisMaster local display:
1.
Press the left button to navigate to the Operator Menu.
2.
Navigate and select Diagnostics.
Figure 7-1: CoriolisMaster Diagnostics on the LCD
3.
Scroll down, locate, and select Output Readings.
4.
Scroll down and locate the DO 41/42 Freq (Dig.Out 41/42 Freq.) parameter.
5.
Record the displayed value.
1000 Hz.
Figure 7-2: ABB CoriolisMaster DO 41/42 frequency output
8

Verify input detection at the HSPC module

This procedure verifies that the HSPC module receives pulse inputs from the CoriolisMaster.
Prerequisites:
HSPC module and CoriolisMaster are connected and powered.
To verify pulse detection by the module:
On the PCCU navigation tree, expand ONLINE, then select TFIO 8/HSPC I:00.
1.
Select the Pulse Counts tab.
2.
3.
Verify that the PI 1 Pulse Count matches the frequency output displayed by the CoriolisMaster
LCD.
for a link).
Figure 7-2
shows an example of a DO 41/42 frequency output of
21 08 74 4MN A A | HS P C C ON FIG UR AT IO N G UI DE | 9