5. Technical data
Measuring input
Input variable and measuring range configured
DC current:
Type 809 – xx1
Start value/final value between
– 100 and 100 mA, R
Any point may be zero
Type 809 – xx2
Start value/final value between
– 1.5 and 1.5 mA, R
Any point may be zero
DC voltage:
EEx version max. 30 V
≤ ± 1.7 V, R
> ± 1.7 to ≤ ± 100 V, R
> ± 100 to ± 1000 V, R
Reduced safety
Measuring output
DC current*:
Programmable,
reference range – 20 ... 20 mA,
start and final values anywhere within the refe-
rence range, also with reversed direction, e.g.
20 ... 4 mA
External resistance:
R
ext
DC voltage*:
Programmable,
reference range – 10 ... 10 V,
start and final values anywhere within the refe-
rence range, also with reversed direction, e.g.
+ 10 ... – 5 V
Load capacity:
R
ext
Programming connector on isolating amplifier
Interface:
Serial interface
Power supply
DC, AC power pack (DC or 45...400 Hz)
Rated voltages and permissible variations
Nominal voltage U
Tolerance
N
24 ... 60 V DC, AC
DC – 15 ... + 33%
AC ± 15%
85 ... 230 V** DC, AC
DC – 15 ... + 33%
24 ... 60 V DC, AC
AC ± 15%
85 ... 230 V AC
± 10%
85 ... 110 V DC
– 15 ... + 10%
≤ 1.2 W resp. ≤ 2.5 VA
Power consumption:
Light emitting diodes
Green LED:
Light after switching on the power supply
Output contact
(Option)
Relay:
For monitoring the measured value limit
1 galvanically isolated switching contact
AC: ≤ 2 A / 250 V (500 VA)
Contact rating:
DC: ≤ 2 A / 125 V (60 W)
Material:
Gold flashed silver alloy
Trip point type:
Programmable as low or high trip point
Trip point of measured variable
Low trip point
G
H
GW
S
H Hysteresis
G Safe condition
Fig. 4. Switching function, according to trip point type.
Trip point adjustment
with PC for trip point:
Programmable between – 10 and 110%***
2
= 15.4 Ω
i
= 1 kΩ
i
= 1 MΩ
i
= 540 kΩ
i
= 5.5 MΩ
i
max. ≤ 600 Ω with 20 mA output
min. ≥ 1000 Ω with 10 V output
Instruments version
Standard (Non-Ex)
Type of protecion
"Intrinsic safety"
[EEx ia] IIC
High trip point
S
GW
H
G
GW Trip point
S
Alarm condition
Hysteresis:
Programmable between > 0 and 100%***
Energizing and de-
energizing delays:
Programmable between 0 to 1080 s
Relay contact position:
Programmable
Frontplate signals:
The green LED "ON" flashes when the limit value
is exceeded
*
The type of output variable (current or voltage) is configurable with software
**
An external supply fuse must be provided for DC supply voltages > 125 V
*** In relation to the analog output value range
6. Mounting
The SINEAX TV 809 can be mounted on a top-hat rail.
When deciding where to install the isolating amplifier (measuring
location), take care that the limits of the operating tempera-
ture are kept:
– 25 and + 55 °C
Simply clip the device onto the top-hat rail (EN 50 022) (see Fig. 5).
Fig. 5. Mounting onto top-hat rail 35 × 15 or 35 × 7.5 mm.
7. Electrical connections
The connections for the leads are fixed or plug-in screw terminals, depending
on the device execution. These are easily accessible at the front of the isolating
amplifier and are suitable for a wire cross-section of max. 2.5 mm
Make sure that the cables are not live when making the
connections!
Impending danger by high input voltage or high power
supply voltage, 250 V at contact output.
Also note that, ...
... the data required to carry out the prescribed measurement
must correspond to those marked on the nameplate of SINEAX
TV 809 (
measuring input,
power supply)!
... the resistance in the output circuit may not overrange the
current output value
R
max. [kΩ] =
ext
I
AN
(I
= current output value)
AN
and not underrange the voltage output value
U
min. [kΩ] ≥
R
ext
10 mA
(U
= voltage output value)
AN
... the measurement input and output cables should be twisted
pairs and run as far as possible away from heavy current
cables!
In all other respects, observe all local regulations when selecting
the type of electrical cable and installing them!
In the case of "Intrinsically safe" explosion-proof,
the supplementary information given on the type exa-
mination certifications, the EN 60 079-14, and also
local regulations applicable to electrical installation in
explosion hazard areas must be taken into account.
measuring output and
12 V
[mA]
[V]
AN
.
2