esera automation auto connect 11324 Руководство пользователя - Страница 6

Просмотреть онлайн или скачать pdf Руководство пользователя для Шлюз esera automation auto connect 11324. esera automation auto connect 11324 8 страниц. 1-wire gateway 10 modbus rtu

esera automation auto connect 11324 Руководство пользователя
14
Software
Data interface Modbus RTU and ESERA ASCII text protocol
The Ethernet interface can be configured using the Windows ESERA program Config Tool 3. This program
can be found in the download area of the ESERA online shop.
14.1
Configuration and Communication with 1-Wire Gateway 10
The 1-Wire Gateway 10 has extensive configuration and formatting options, which can be read out and
operated with the ESERA Config Tool 3.
Since communication between 1-Wire Gateway 10 and Config Tool 3 takes place via the open ESERA ASCII
text protocol, you can also exchange data with any terminal program (e.g. Hercules or Putty) at any time via
UDP / RTU with the 1-Wire Gateway 10 and carry out the configuration.
Details about the communication commands can be found in the document "Programmer's Guide" in the
download area of the article on our website, www.esera.de and within Config Tool 3.
15
Communication
15.1
ESERA ASCII Text Protocol / Programming Manual
The 1-Wire Gateway 10 provides two protocols. The ESERA text protocol in ASCII format can easily be used for
configuration and analysis. Special attention has been paid here to good legibility and traceability for people. The
ESERA text protocol works with "GET" and "SET" commands, which probably every programmer has already
used in his own projects.
The ESERA text protocol is completely open and documented. The current version of the programming manual
can be found in the article download area of our website and via the configuration software ESERA Config Tool 3.
15.2

Modbus Protocol

You can communicate with the 1-Wire Gateway 10 without switching over the ESERA Text or Modbus RTU
protocol. The IP address and the port for the communication can be freely selected. The default settings are Port
5000 and DHCP operation.
The Modbus protocol has a standardized structure.The following is a small excerpt of the addressing overview.
The complete addressing overview can be found in
10.
Extract Mode Address Description
Description
Gateway No.
Article No.
Firmware Version
Hardware Status
serial number
time
date
...
1-Wire Bus Sensors
and Actuators
OWD 1 /1-Wire Module
OWD 2 /1-Wire Module
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
EXCEL
read address
60000
60001
61000
61010
61020
61030
61035
40100
40101,40102
40103,40104
40105,40106
40107,40108
40109,40110
40111,40112
40113,40114
40115,40116
40200
40201,40202
40203,40204
...
11324 V2.0 R1.0 Manual
format in the download area of the 1-Wire Gateway
Number of words
(16Bit)
1
1
4
3
9
4
4
1
2
2
2
2
2
2
2
2
1
2
2
data type
Word
Word
String
String
String
String
String
Integer
DWord 1
DWord 2
DWord 3
DWord 4
DWord 5
DWord 6
DWord 7
DWord 8
Integer
DWord 1
DWord 2
Page 6 of 8