Camlogic PFG-06/TC Установка и обслуживание - Страница 2

Просмотреть онлайн или скачать pdf Установка и обслуживание для Промышленное оборудование Camlogic PFG-06/TC. Camlogic PFG-06/TC 2 страницы. Capacitive level gauges

ELECTRICAL WIRING
Diameters of 0.5 mm² to 1.5 mm² are sufficient for the connecting cables owing to the low current values applied.
In any case the section must prevent the current density from exceeding 4 A/mm² in each conductor. The cross-section
of the conductors must also be adequate in relation to the lenght of the cable used to avoid a drop in the voltage
along the cable over the values prescribed by the regulations on the subject.
One of the conductors is solely used for the earthing of the capacitive
level gauge PFG-06. It is likewise recommended to use flexible cables with
an adequate outside diameter for the cable entries used (not supplied)
to ensure a perfect seal of the cable clamp on the power supply and
signal carrying cable.
Use exclusively cable entries certified according to the directive 2014/34/EU
Category 2 and EN 60079-31.
CAUTION :
In the terminal board compartment, the connection for
Faston type cable terminal whose position is marked by the symbol
on the printed circuit (Fig. 1) is used for the earthing of the level gauge.
The yellow-green conductor (only green for the USA) of the power cable
must be connected to this terminal.
The ground connection of the level gauge, through the yellow-green
conductor, is compulsory.
-
The external earthing has to be carried out by the installator.
-
The equipment has to be protected against impact and electrostatic
inside the silo.
-
The user has to protect the equipment circuits with fuses against short
circuit.
- The max. surface temperature considered is without dust and not safety
distance.
Inside the cover there is the wiring plate (Fig. 2) which has printed on it the wiring diagram for the power supply and
use of the level gauge.
ø102
ø28
PFG-06
ø88
ø102
ø28
PFG-06/TC
ø88
The manufacturer CAMLogic declares under its own responsability that the product PFG-06/. answers to the requisites
of the European Directive 2014/34/EU in consideration of the standards: EN IEC 60079-0:2018, EN 60079-31:2014.
Marking:
II 1/2D Ex ta/tb IIIC T90°C IP65 Da/Db - The permitted ambient temperature range from -20 to +70 °C.
Notified corporate body that releases the examination TÜV ITALIA. Certificate number TÜV IT 13 ATEX 071.
Corporate body entrusted of the periodic overseeing TÜV ITALIA.
Instructions Manual No. 01701 25.12 - Rev. 01
no part of it may be disclosed without written authorization from CAMLogic.
This manual, even after the sale of the level gauge, is lent and remains the property of the Manufacturer.
SGC2012
REFERENCE FIGURES
SW 52
ø32
INTERVENTION
DISTANCE 0-25 mm.
ø38.1
ø50.4
EU
DECLARATION OF CONFORMITY
Always check that the mains voltage and
frequency correspond to those given on the
plate of the level gauge before powering it.
The power cable must be fixed to the main by
a qualified installer in compliance with the
current safety standards in merit.
For electric connections to the terminal use
Faston cable terminals ( 6.3 x 0.8 mm. ).
MAINTENANCE
Capacitive level gauge PFG-06 needs no routine
ø1"1/2 Gas
maintenance.
WARRANTY
CAMLogic, in addition to the terms of the supply
Sensor area
contract, guarantees its products for a period
of twenty-four (24) months from the date of
shipment.
This warranty is expressed only in the repair
or replacement free of charge of parts that,
after careful examination by the Manufacturer,
turn out to be defective.
Warranty, excluding all liability for direct or
ø32
indirect damage, is considered to be restricted
to only defects in materials and has no effect
PFG-06/F
if the parts returned turn out to have been
anyhow dismantled, tampered with or repaired
by anyone other than the Manufacturer.
Warranty likewise excludes damage deriving from
negligence, carelessness, bad or improper use
of the level gauge, or from bad handling by the
operator and faulty installation.
Moreover, warranty is forfeit if non-genuine spare
ø120
parts have been used.
A returned level gauge, even if under warranty,
ø140
must be shipped carriage free.
All the informations contained in this manual are confidential and
R1
4
5
6
R2
7
8
9
R1
4
5
6
R2
7
8
9
Fig.3
01701 25.12 - Rev. 01