AKO 55424 Руководство пользователя - Страница 7
Просмотреть онлайн или скачать pdf Руководство пользователя для Система безопасности AKO 55424. AKO 55424 12 страниц. Trapped person alarm
5.- Configuration
Input auto-detection
Step 1
When receiving a power supply for the first time, the alarm enters
INPUT AUTO-DETECTION MODE, lighting up the input indicators
sequentially in green.
Step 2
Begin AUTO-DETECTION by pushing the 'AUTOCONFIG' push-button
for 5 seconds (See page 4). At the end of the process, the alarm will
emit 5 short beeps and will begin to function normally.
For correct input detection, all devices must be correctly
connected and in NO ALARM mode.
Once the alarm has been configured, this function will not
be activated again. To activate it again, disconnect the
power supply, connect it again and press the
"AUTOCONFIG" pushbutton 5 times consecutively within 2
minutes and repeat step 2 within another 2 minutes.
Self-diagnosis function
The device incorporates a self-diagnosis system which informs the user in the event of a push-button malfunction
or if there are wiring errors.
If a malfunction is detected, the alarm will emit 3 short beeps every 2 minutes and the corresponding input
indicator will flash red.
MODBUS parameter reset
To revert MODBUS parameters to factory settings, activate the INPUT AUTO-DETECTION function and press the
'AUTOCONFIG' push-button 5 consecutive times.
MODBUS parameters can only be modified using AKONET software.
1
ON
OFF
2
7
5542H402 Ed.03