Wiring
4. Wiring
The transmitter is connected in accordance with the wiring diagram (Fig. 4.1) considering
the load resistance requirements.
►
NOTICE
Signal cables should be routed separately or screened from the supply cables.
►
NOTICE
Only a shielded cable may be used for the signal lines.
Use the diagram (Fig. 4.2) to select the permissible load resistance.
Recommendation:
R = 500 ± 50 ohm
Switch on the power supply only after the wiring of the device has been complete-
►
NOTICE
ly performed.