Anderson 80G200 Kullanım Kılavuzu - Sayfa 11

Brülör Anderson 80G200 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Anderson 80G200 17 sayfaları.

from the appropriate SSA80 burner table to set the differential air pressure needed
at high fire.
3.
Set the system to low fire air. Drive to low fire position. Measure pressure with
manometer set to 0.5mbar. This is the initial setting only. Further adjustment may
be required.
4.
Make sure all the settings are still the same after you cycle the system several times
between high and low fire.
5.
Burner ignition: open all the manual cocks, make sure air blower is running, the
automatic control valve is driven to low fire by flame controller, spark start ignition,
gas valve open and flame on, flame signal feedback to the controller, adjust gas
and combustion pressure by the opening of valve till strong flame signal send back
to flame controller.
6.
High fire gas setting: drive burner to high fire, set gas pressure difference between
burner and chamber according to the datasheet of relative type of burner. Then
drive burner to low fire and back to high fire again to check the pressure difference.
Several recycles till the pressure difference not change again.
7.
Low fire gas setting: Drive the system to low fire. Setting low fire gas pressure
difference according to datasheet of relative type of burner This is target value for
low fire. Drive burner to high fire then goes back to low fire to check pressure
difference. Several recycles of low and high fire change till the pressure difference
not change again.
NOTE:
It is very difficult to measure the very low pressures experienced at low fire,
and it may be necessary to rely on visual inspection. This is especially true when
gas turndowns in excess of 10:1 are being used. The main intent is to provide a
clean stable flame with a good flame signal that will not cause the furnace
temperature to overshoot.
8.
Verify the Gas Settings: Make sure that all settings are still the same after cycling,
the system several times between high and low fire.

10.9 start burner

1.
Start blower.
2.
Open all the valves including automatic and manual valves.
3.
Start ignition procedure.
4.
Confirm the ignition procedure finished then control valve opening is controlled
by 4-20mA.

10.10 Stop Procedure

Do not turn the combustion air blower off until the chamber temperature is below
120 °C. This will prevent hot gases from back flowing into the burner and blower
causing damage to the burner.
1.
Stop the burner through the burner control system.
2.
Run the combustion air blower until the chamber temperature drops below 80 °C.
3.
Shut off the combustion air blower.
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – SSA80 Operation Manual
9