Figure 5). The U141v+'s address must be the
same as its FB number in the UNI.
For example, if the module's FB number is
nine, set the tens switch to zero and the ones
switch to nine.
Figure 5. Dual Rotary Address Switches
The U141v+'s BACnet Device Instance
number can be assigned by the UNI or
individually specified. This number is shown
on the UNI Properties page in WebCTRL or on
the UNI Status page in SuperVision.
Power Wiring
The Unet follows the same specifications as a
legacy CMnet. Refer to the Technical
Handbook for details on legacy CMnets. Also
refer to the Technical Handbook for detailed
information on daisy-chain, star, and hybrid
wiring configurations.
There is a special wire available that contains
a pair of 14AWG wires for power and a pair of
22AWG wires for communication. This wire is
available from:
Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Product number A3U-LINE
CAUTION The U141v+ modules are Class 2
devices (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting a U141v+ module in a control panel
where Non-Class 2 devices (120V and
greater) or wiring are present.
You can power several modules from the
same transformer by daisy-chaining the
Revised 8/14/02 • U141v+
power from one U-Line module to the next,
using the two power connections on the
U141v+ (one for incoming power and the
other for continuing the wiring to the next U-
card). You must maintain the same polarity.
Do not exceed 100VA or 500 feet (152.4
meters) total of 14AWG wire. The maximum
number of modules on one transformer can
be figured by dividing the VA of the
transformer by the sum of the VA of the
module plus the VA of any accessories. For
example, if the module's power is 9VA,
accessories per module equal 6VA, and the
transformer is 100VA, you could have up to 6
modules on the network. See the formula in
Figure 6 and the example in Figure 7.
VA (transformer)
VA (module) + VA (accessories)
Figure 6. Figuring Maximum Number of Modules
100VA
9VA + 6VA
Figure 7. Example of Figuring Maximum Number
of Modules
The U141v+ has an operating range of
21.6VAC to 26.4VAC. Whenever possible,
connect and verify power and
communications to all modules before
connecting any inputs or outputs.
1. Remove the U141v+'s power jumper or
place it in the off position. This prevents
the module from being powered up before
verifying correct voltage.
2. Make sure the 24VAC power source is off.
3. Connect the power wires to the module's
power terminals labeled 24VAC and Gnd.
4. Turn the 24VAC power source on.
5. Make sure that 24VAC is present at the
module's power input terminals.
5
© 2002 Automated Logic Corporation
Maximum #
=
of modules
(rounded down)
=
6.67 or
6 modules maximum