Automated Logic U141v+ Teknik Talimatlar - Sayfa 7
Kontrol Sistemleri Automated Logic U141v+ için çevrimiçi göz atın veya pdf Teknik Talimatlar indirin. Automated Logic U141v+ 12 sayfaları.
To communicate through the LogiStat port,
the U141v+ must:
• be connected to a UNI on an ARC156
network segment
• use the appropriate module driver
For SuperVision systems, use a version
6.01d or later of the U1M, U3M, U5M, or
UNM module driver
Communication speed is fixed at 1200 baud.
1. Connect the computer's serial port to the
EIA-232 port of the APT using a standard
straight-through cable.
2. Set the APT's Mode Select switch to TTL
(see Figure 9 on page 7).
If you are using a LogiStat Plus without
supplemental power to the APT, make
sure the LED on the Logistat Plus is on
indicating that it can provide power to the
APT. If the LED is not on, you can provide
power to the APT using the Supplemental
Power +5V dc connection (see Figure 9 on
page 7) and the special power cable to a
laptop keyboard jack, or an external
supply, such as a 5V dc transformer.
3. Define the connection type.
In SuperVision v3.0, define the connection
as Access Port.
In SuperVision v2.6, define the connection
as Direct Connect.
4. Set the baud rate at 1200 bps.
5. Attach the LogiStat Adaptor cable (ALC
part number 235022) to the APT cable.
Use this assembly to connect the APT's
Access Port to the LogiStat's LogiPort.
While connected, the LogiStat Pro
displays "LP" indicating that the LogiStat
Pro will not respond to input from the
keypad.
Revised 8/14/02 • U141v+
Enc los ed E ner gy
M anagem ent E quipm ent
R
88FO
E 1439 0
T YP E : 00 3410
0
A
U T O M A T E D
C
O
R
P
O
U 141 v+
CAU TION:
To Red uc e T he Ris k of F ir e
or E lectric S hock , Do No t
Inter c onnect the Outputs of
Diffe rent Clas s 2 Cir c uits .
CA UT ION :
This produc t was des igne d
to b e m ounted inside
the building envelope .
Warr anty voided
if m ounte d outside.
L o
F lo w
EIA-232
Port
Figure 9. Using the LogiPort
NOTE When the LogiStat Adaptor cable
is inserted into the LogiPort, the U141v+
can no longer read the LogiStat inputs.
The U141v+ continues to use the last valid
temperature and setpoint adjust readings
obtained before the cable was inserted
into the LogiPort. If the occupancy
override timer was active when the
connection was made, it continues to
count down, but no new values can be
obtained for these inputs until the
LogiStat Adaptor cable is removed. See
the Eikon for WebCTRL Microblock
Reference Guide or the Eikon Microblock
Reference Guide for more information
about the LogiStat microblock.
6. Disconnect the LogiStat Adaptor cable
from the LogiStat's LogiPort when
finished to allow the U141v+ to read
inputs from the LogiStat.
Input Wiring
The U141v+ inputs support the types of
signals listed below. The LogiStat, LogiStat
Plus, and LogiStat Pro sensors are supported
through the module's LogiStat port. Refer to
7
© 2002 Automated Logic Corporation
C las s 2
24 V ac
G n d
P ow e r
G n
5 0-60 H z
24 V ac
2 4 Va c
d
7VA
0.29A
Us e Cop per
O n
O ff
Conduc tors
Only
R x
Tx
L
O G IC
E rr o r
R
R
A
T
I
O
N
R u n
O utput
24V Max , 1A M ax
2
DO-
1
1
G nd
G n
IN-
d
+ 1 0
Input: 5V Max
G nd
2
V
A O : 0-10 Vd c
G n
5m A
IN-
d
Ma x
AO-
1
1
C C W
L S 5 v
TM
B A C ne t
S
M o t or
M S /T P
w
D ir
Te m
p
.
H
G n d
C W
i
LogiStat
LogiStat
Port
LogiStat Adaptor Cable
Exec. 4 Relay
Switch
Supplemental
E xec. 4 relay
Power
Isolate Network
+5V dc
A P T
5
9
ACCESS
PORT
6
1
Mode Select
2- T x out
3- R x in
Rx
Tx
+5V
5- G nd
485
TTL
1,6,8- +10V or floating
Mode Select
Switch
Access
Port