To verify each output's operation, lock the
output to a known condition using the
Function Block's Properties page in WebCTRL
or the Parameter page in SuperVision, then
make sure the equipment operates as
specified.
Analog Output Wiring
The U141v+ has one analog output that
supports voltage devices from 0 to 10VDC
(see Figure 13). The device being controlled
must have a minimum of 2000 Ohms
resistance measured from its input to ground
and must share the same ground as the
module.
Gnd
AO-1
Figure 13. Analog Output Wiring
Be sure the U141v+'s power is off before
wiring any inputs or outputs. Connect the
output wiring to the screw terminals on the
module.
To verify each output's operation, lock the
output to a known condition on the Function
Block's Properties page in WebCTRL or the
Parameter page in SuperVision, then make
sure the equipment operates as specified.
Using Flow Sensors
The U141v+ controls air flow in the zone
using:
• the built-in actuator and flow sensor
You must indicate Configuration 1 for the flow
control on the UNI module driver's Parameter
page. Refer to the UNI/30 or UNI/59 Technical
Instructions for details.
To connect the sensor, make sure the
U141v+'s power is off first. Attach the total or
Revised 8/14/02 • U141v+
-
0 to 10V
+
high pressure line from the VAV box to the
module's HI side, and attach the static
pressure line to the module's LO side. To
ensure an accurate reading from the flow
sensor, use the Airflow microblock in the
module's GFB. You must calibrate this
microblock using the instructions on the FB's
Properties page in WebCTRL or Parameter
page in SuperVision. Refer to the Eikon for
WebCTRL Microblock Reference Guide or the
Eikon Microblock Reference Guide for more
information.
Writing GFBs for the U1 41v+
Depending on whether you are using a
WebCTRL or a SuperVision system, you must
use either Eikon for WebCTRL or Eikon 3.0a
or later to create GFBs for the U141v+. Be sure
to enable the Zone GFB option in Eikon when
making the GFB.
A sample U-Line GFB is available at
Automated Logic Corporation's web site
(http://www.automatedlogic.com). Use this
sample as a guideline for creating your own
GFBs. A default algorithm can be loaded into
the U-card to provide stand-alone control
functions if communications between the U-
card and the UNI are disrupted. Refer to the
appropriate UNI module driver technical
instruction for instructions on setting up this
default algorithm. The U141v+'s Graphic
Function Block is stored in the UNI module,
which must use one of the following module
drivers:
• For WebCTRL systems, the DRV_UNI16
or DRV_UNI32 module driver.
• For SuperVision systems, the U1M,
U3M, UNM, or U5M module driver. A
sample GFB is also shown in Figure 14
on page 12.
When using a LogiStat sensor with the
U141v+, include a LogiStat microblock and a
Zone Control microblock in the module's
9