Power and protection
Device requires 9...24 V DC power supply and consumes, depends of the voltage from 94mA at 9V to
35mA at 24V. Device has a diode protection against wrong power wiring polarity.
All device inputs (power, DH+, Ethernet) are TVS protected from spikes and transients.
Connections
To connect ANC-100e device to your existing DH+ network or directly to another DH+ device, please
use one of the connectors included with the product.
1. Connect the DH+ cable to the ANC-100e left most and right most terminals of the Phoenix
3 pin connector leaving the middle pin not connected. The polarity of blue and clear cables
does not matter
2. Connect ANC-100e to the Ethernet network or a free Ethernet port on the computer or a
free Ethernet port on a network hub/switch
3. The "Ethernet" LED light should blink intermittently for a moment
4. The "DH+" light will blink every 3 seconds indicating that the device is connected and
associated to a DH+ network
Due to ANC-100e unique DH+ Polarity Detection feature, the way the individual conductors (1/2) are
connected does not matter, since upon startup, ANC-100e will AutoDetect and configure itself to use the
correct polarity for communication regardless of the DH+ cable polarity.
LED Diagnostics
ANC-100e is equipped with three LEDs used for visual status and diagnostic display.
LED labeled "Ethernet" indicates the data exchange between the ANC-100e and the user PC or any
device on the Ethernet network. When the device sends/receives a packet to/from the PC/Ethernet
Network, this LED blinks indicating packet exchange.
LED labeled "Diag" indicated the current status of the ANC-100e device on the DH+ network:
•
"LED Solid Red" indicates that the device is not currently associated on a DH+ network.
•
"LED Solid Green" indicates that the device is associated on the DH+ network
©Automation Networks & Solutions LLC. 2016
Connect the power supply + and – wires to the appropriate
connection points on the power connector supplied with
the device. Please reference the figure on the left for proper
wiring.
System grounding in most cases is not necessary but may be
useful for protection against high power spikes.