Section III. Carbon Matrix Installation

1) Unlatch and open the empty carbon matrix tray adjacent to the polarized-media air cleaner.
2) Leaving the protective foam border in place, carefully place the carbon sections into the tray
as shown below. The carbon matrix should be positioned downstream of the polarized-media
air cleaner in order to extend the service life of the carbon.
3) Close and latch the carbon tray. Secure the latches with screws (provided) for extra security.
4) Close the cabinet access door and latch securely.
5) Turn on the power to the furnace/air handler and UV lamp. The thermostat fan switch should
be set to the "ON" position.
6) Affix the caution label and Replacement Record sticker in prominent locations to the cabinet.
IMPORTANT: FOR BEST AIR CLEANING EFFICIENCY AND OPTIMUM COMFORT, THE FURNACE/AIR
HANDLER FAN SHOULD BE RUN CONTINUOUSLY WITH THE FAN SWITCH IN THE "ON" POSITION
RATHER THAN THE "AUTO" POSITION.

Section IV. UV Lamp Installation

1) The model 407H-16 or the 407H-16-O3 Series2 Germicidal UV Lamp is standard on some
models or available separately.
2) Remove the cover from the unit by removing the top and bottom retaining screws using a
screwdriver.
3) Remove the knock-outs on the RS4 cabinet door for UV lamp and safety switch (fig 1).
4) Attach back of the UV unit to the cabinet door using the four ¼" 8-32 screws provided.
5) Attach ¾" 8-32 safety switch screw to cabinet frame (fig 8) to activate safety switch.
6) Remove germicidal lamp holder using a 11/32 size nut driver (fig 9).
7) Slide germicidal lamp into lamp opening and reinstall lamp holder.
8) Plug lamp into lamp connector.
9) Connect power in accordance with local wiring codes. The multivoltage ballast is self-adjusting
and operates with voltages from 120 - 240 VAC. Use the provided 120 VAC power cord. For
240 VAC, install 5 amp inline fuses and use the optional 240 VAC power cord, Part #PC-240.
IMPORTANT: WHEN USING THE 407H-16-O3 LAMP WITH ACTIVATED OXYGEN, POWER TO THE
LAMP MUST BE INTERLOCKED WITH THE FURNACE BLOWER.
Figure 7. Airflow can
be in either direction