LINE SET, DRAIN TUBE, and ELECTRICAL CONNECTIONS

Line set, drain tube and electrical connections have been relocated to be accessible from the bottom (cellar side / grille
side) located on return side of unit.
Can be accessed by removing the grille.
Flare fittings have been added to the line set.
Liquid line – ¼" flare fitting.
Suction line – ½" flare fitting.
Connect Flare nuts from line set to system using Crescent wrenches or torque wrench.
Pressure test is mandatory after connecting line set to the unit.
• Verify there are no leaks before beginning vacuum and charging process.

ADDITIONAL ACCESS HOLES

Top access holes.
• 1 large hole for line set.
• 1 small hole for electrical.
• Note: do not run electrical wiring through same hole as line set.
Side access holes.
• 1 large hole for line set.
• 1 small hole for electrical.
• Note: do not run electrical wiring through same hole as line set.
Use the provided plug to cover the small hole not in use.
Use the provided sticker (4" x 4") to cover the large hole not in use.
Use the provided strain relief clamp to route electrical wiring into unit.
Seal around line set hole with cork tape, or other insulation to ensure proper seal.
Note: side access holes will be applicable only if utilizing the flush mounting option.