Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Decimal
Input type
Display
point
1
K (CA)
KCaH
0.1
KCaL
1
J (IC)
JIcH
0.1
JIcL
1
E (CR)
ECrH
0.1
ECrL
1
T (CC)
TCcH
0.1
TCcL
B (PR)
1
Thermo
B PR
R (PR)
1
-couple
R PR
S (PR)
1
S PR
N (NN)
1
N NN
C (TT)
1
01)
C TT
G (TT)
1
02)
G TT
1
L (IC)
LIcH
0.1
LIcL
1
U (CC)
UCcH
0.1
UCcL
Platinel II
1
PLII
Cu50 Ω
0.1
CU 5
Cu100 Ω
0.1
CU10
1
JPt100 Ω
JPtH
0.1
RTD
JPtL
DPt50 Ω
0.1
DPT5
1
DPt100 Ω
DPtH
0.1
DPtL
Nickel120 Ω
1
NI12
0 to 10 V
-
AV1
0 to 5 V
-
AV2
1 to 5 V
-
Analog
AV3
0 to 100 mV
-
AMV1
0 to 20 mA
-
AMA1
4 to 20 mA
-
AMA2
01) C (TT): Same as existing W5 (TT) type sensor
02) G (TT): Same as existing W (TT) type sensor
• Permissible line resistance per line: ≤ 5 Ω
■ Display accuracy
Input type Using temperature Display accuracy
(PV ±0.3% or ±1 ℃ higher one) ±1-digit
• Thermocouple K, J, T, N, E below -100 ℃ and L, U, PLII, RTD Cu50 Ω,
At room temperature
DPt50 Ω: (PV ±0.3% or ±2 ℃ higher one) ±1-digit
(23℃ ±5 ℃)
• Thermocouple C, G and R, S below 200 ℃:
Thermo
(PV ±0.3% or ±3 ℃ higher one) ±1-digit
• Thermocouple B below 400 ℃: There is no accuracy standards
-couple
(PV ±0.5% or ±2 ℃ higher one) ±1-digit
RTD
• RTD Cu50 Ω, DPt50 Ω: (PV ±0.5% or ±3 ℃ higher one) ±1-digit
Out of room
• Thermocouple R, S, B, C, G:
temperature range
(PV ±0.5% or ±5 ℃ higher one) ±1-digit
• Other sensors: ≤ ±5 ℃ (≤-100 ℃)
At room temperature
±0.3% F.S. ±1-digit
(23℃ ±5 ℃)
Analog
Out of room
±0.5% F.S. ±1-digit
temperature range
• In case of TK4SP Series, ±1 ℃ will be added to the degree standard.
Unit Descriptions
1
4
2
3
4. Indicator
Display
Name
Description
℃, %, ℉ Unit
Displays selected unit (parameter)
AT
Auto tuning Flashes during auto tuning every 1 sec
Turns ON when the control output is ON
• SSR output (cycle/phase control)
Control
MV over 5% ON
OUT1/2
output
• Current output
Manual control: 0% OFF, over ON
Auto control: below 2% OFF, over 3% ON
Alarm
AL1/2
Turns ON when the alarm output is ON
output
Manual
MAN
Turns ON during manual control
control
The SV indicator is ON which is currently
SV1/2/3
Multi SV
displayed. (When using multi SV function)
• For the details about old model, refer to the user manual. Download the manuals from the Autonics website.
Using range (℃)
Using range (℉)
-200 to 1,350
-328 to 2,463
-199.9 to 999.9
-199.9 to 999.9
-200 to 800
-328 to 1,472
-199.9 to 800.0
-199.9 to 999.9
-200 to 800
-328 to 1,472
-199.9 to 800.0
-199.9 to 999.9
-200 to 400
-328 to 752
-199.9 to 400.0
-199.9 to 752.0
0 to 1,800
32 to 3,272
0 to 1,750
32 to 3,182
0 to 1,750
32 to 3,182
-200 to 1,300
-328 to 2,372
0 to 2,300
32 to 4,172
0 to 2,300
32 to 4,172
-200 to 900
-328 to 1,652
-199.9 to 900.0
-199.9 to 999.9
-200 to 400
-328 to 752
-199.9 to 400.0
-199.9 to 752.0
0 to 1,390
32 to 2,534
-199.9 to 200.0
-199.9 to 392.0
-199.9 to 200.0
-199.9 to 392.0
-200 to 650
-328 to 1,202
-199.9 to 650.0
-199.9 to 999.9
-199.9 to 600.0
-199.9 to 999.9
-200 to 650
-328 to 1,202
-199.9 to 650.0
-199.9 to 999.9
-80 to 200
-112 to 392
0 to 10 V
0 to 5 V
1 to 5 V
0 to 100 mV
0 to 20 mA
4 to 20 mA
1. PV display part (Red)
• Run mode: Displays PV (Present value).
• Setting mode: Displays parameter name.
2. SV display part (Green)
• Run mode: Displays SV (Setting value).
• Setting mode: Displays parameter setting value.
3. Input key
Display
Name
[A/M]
Control switching key
[MODE]
Mode key
[◀], [▼], [▲]
Setting value control key
TK4N Series
Other series
5. PC loader port:
For connecting
communication
converter (SCM series).
Dimensions
• Unit: mm, For the detailed drawings, follow the Autonics website.
• Below is based on TK4S Series.
A
Body
A
B
TK4N
48
24
TK4S
48
48
TK4SP
48
48
TK4M
72
72
TK4W
96
48
TK4H
48
96
TK4L
96
96
■ Bracket
TK4N
42
45.2
48.6
■ Terminal protection cover
TK4N
44.6
6.2
Installation Method
■ TK4N
After mounting the product to panel
with bracket, fasten the bolts by
using screwdriver.
Errors
Display Input
Temperature
sensor
5
OPEN
Analog
Temperature
sensor
HHHH
Analog
Temperature
sensor
LLLL
Analog
Temperature
sensor
ERR
Analog
C
D
E
C
D
E
F
3
91.8
-
21.8
6
64.5
1.7
45
6
72.2
-
44.8
6
64.5
1.7
67.5
6
64.5
1.5
44.7
6
64.5
1.5
91.5
6
64.5
1.5
91.5
TK4S/SP
□49.5
32.4
26.4
10
60.3
■ Other series
Screwdriver
Insert the unit into a panel, fasten the bracket by
pushing with a flathead screwdriver.
Description
Output
Flashes at 0.5 sec interval when
'Sensor error,
input sensor is disconnected or
MV' parameter
sensor is not connected.
setting value
'Sensor error,
Flashes at 0.5 sec interval when
MV' parameter
input is over F.S. ±10%.
setting value
Flashes at 0.5 sec intervals if the
Heating: 0%,
input value is above the input
Cooling: 100%
range.
Flashes at 0.5 sec intervals if the
input value is over 5 to 10% of high
Normal output
limit or low limit value.
Flashes at 0.5 sec. intervals if the
Heating: 100%,
input value is below the input
Cooling: 0%
range.
Flashes at 0.5 sec intervals if the
input value is over 5 to 10% of low
Normal output
limit or high limit value.
Flashes at 0.5 sec intervals if there
is error for setting and it returns to
-
the error-before screen.
■ Panel cut-out
G
I
Panel cut-out
G
H
I
J
≥ 55
≥ 37
45
22.2
+ 0.6
+ 0.3
0
0
≥ 65
≥ 65
45
45
+ 0.6
+ 0.6
0
0
≥ 65
≥ 65
45
45
+ 0.6
+ 0.6
0
0
≥ 90
≥ 90
68
68
+ 0.7
+ 0.7
0
0
≥ 115 ≥ 65
92
45
+ 0.8
+ 0.6
0
0
≥ 65
≥ 115 45
92
+ 0.6
+ 0.8
0
0
≥ 115 ≥ 115 92
92
+ 0.8
+ 0.8
0
0
Other series
30.5
46
12
23.9
Flathead screwdriver
Troubleshooting
Check input
sensor status.
Check analog
input status.
When input is
within the rated
input range,
this display
disappears.
Check setting
method.