Autonics LE4S Series Manuel - Sayfa 5

Zamanlayıcı Autonics LE4S Series için çevrimiçi göz atın veya pdf Manuel indirin. Autonics LE4S Series 6 sayfaları. Lcd digital timers
Ayrıca Autonics LE4S Series için: Talimatlar (18 sayfalar), Manuel (17 sayfalar)

Autonics LE4S Series Manuel
INTG
T
T1
T2
POWER
START
RESET
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
1. Time starts only when START signal: ON
2. START signal: OFF (output: OFF status) → Time: Hold
3. Progressing time = setting time → Output: ON,
display value: Hold
4. RESET signal: ON → Display value and output: return to the
initial status
■ LE4SA
Initial status: UP mode - display value 0, output OFF
DOWN mode - displays the setting time, output OFF
Instantaneous contact (OUT2) return: it is available when the power is OFF.
Release the key lock to use [RESET] key.
• T, T.on, T.off, T1 : setting time / T.out : One-shot output time (range: 0.01 to 99.99 sec) /
Rt: return time
• T2: S-D mode - switching time, TWN, TWN.1 mode - setting time
• T.on, T.off / T1, T2 (TWN, TWN.1 mode): individual setting available
• T, T.on, T.off > Ta
OND
T
POWER
RESET
Time limit contact
Instantaneous contact
Setting time
UP
0
Setting time
DOWN
0
1. Power: ON, simultaneously time starts
2. Progressing time = setting time → Time limit output: ON,
display value: Hold
3. Time limit 1c + Instantaneous 1c mode
: power ON → Instantaneous output ON
power OFF → Instantaneous output OFF
4. RESET signal: ON → Display value and output: return to the
initial status
OND.2
T
POWER
RESET
Time limit contact
Instantaneous contact
Setting time
UP
0
Setting time
DOWN
0
1. Power: ON, simultaneously time starts
2. Progressing time = setting time →
Time limit output: ON (during T.out) and OFF,
display value: Hold
3. Time limit 1c + Instantaneous 1c mode
: power ON → Instantaneous output ON
power OFF → Instantaneous output OFF
4. RESET signal: ON → Display value and time limit output: return
to the initial status
FLK
T.off T.on
T.off
T.on
POWER
RESET
Time limit contact
Instantaneous contact
T.off
T.on
UP
0
T.off
T.on
DOWN
0
1. Power: ON, simultaneously output: repeating OFF (during T.off),
ON (during T.on)
2. Time limit 1c + Instantaneous 1c mode
: power ON → Instantaneous output ON
power OFF → Instantaneous output OFF
3. RESET signal: ON → Display value and time limit output: return
to the initial status
T
T
T
a
b
c
POWER
START
T1
T2
RELAY OUT
Rt
T
T
POWER
T
Time limit
contact output
Rt
T
T
POWER
T
Time limit
contact output
T.off
Ta
Rt
T.off
T.on
T.off
POWER
T.off
T.on
Time limit
contact output
FLK.1
POWER
RESET
Time limit contact
Instantaneous contact
T.off
T.on
UP
0
T.off
T.on
DOWN
0
1. Power: ON, simultaneously output
: repeating ON (during T.on ), OFF (during T.off)
2. Time limit 1c + Instantaneous 1c mode
: power ON → Instantaneous output ON
power OFF → Instantaneous output OFF
3. RESET signal: ON → Display value and time limit output: return
INT
POWER
RESET
Time limit contact
Instantaneous contact
Setting time
UP
0
Setting time
DOWN
0
1. Power: ON, simultaneously time limit output ON and
time starts
2. Progressing time = setting time → Time limit output: OFF,
3. Time limit 1c + Instantaneous 1c mode
: power ON → Instantaneous output ON
power OFF → Instantaneous output OFF
4. RESET signal: ON → Display value and time limit output: return
S-D ( Υ -∆)
POWER
RESET
Υ contact
∆contact
T1
Setting time
T2
UP
0
T1
Setting time
T2
DOWN
0
1. Power: ON, simultaneously Y contact: ON and time starts
2. Progressing time = Setting time T1 → Y contact: OFF,
initializing progressing time and progress again
3. Progressing time = Switching time T2 →
4. RESET signal: ON → Display value and Y -
TWN
POWER
RESET
T1 contact
T2 contact
T1
Setting time
T.out
T2
0
UP
T1
Setting time
T2
DOWN
0
1. Power: ON, simultaneously T1 contact: ON and time starts
2. Progressing time = Setting time T1 → T1 contact: OFF,
T2 contact: ON, initializing progressing time and progressing
T.on
3. Progressing time = Setting time T2 → T1 contact: ON,
4. RESET signal: ON → Display value and T1, T2 contact
T.off
T.on
T.on
T.off
T.on
T.off
T.on
Ta
Rt
to the initial status
T
Rt
T
display value: Hold
to the initial status
T1
T2
Rt
contact: ON, display
value: Hold
contact:
return to the initial status
T1
T2
Rt
T1
again
T2 contact: OFF,
display value: Hold
: return to the initial status
T.on
T.off
T.on
T.off
POWER
T.on
T.on
T.off
T.off
Time limit
contact output
T
POWER
T
Time limit
contact output
T1
T2
POWER
T1
Y contact
T2
∆ contact
T2
T1
POWER
T1
T1 contact
T2
T2 contact